Periodic Inspection
65
Do not pull out the strainer inside as it cannot be disassembled. (For more information, please refer to
the engine instruction manual)
Check Terminal and Wirings
Every 4 months or 500 Hours
Check for any looseness on the cables, any damage on
insulated covers, and disconnection, disconnected cables,
or short-circuits etc.
[Items to check on the generator side]
Terminal connection of 3-phase output terminal plate.
Main circuit of circuit breaker.
Terminal connection on control box.
Each terminal connection of each instrument.
[Items to check on the engine side]
Portion of connectors to the engine.
Check for looseness of terminal connections.
Rubbing and wear of the wire.
Check Exhaust Flexible Pipe
Every 4 months or 500 Hours
Check the flexible pipe between the DOC
and engine exhaust outlet for cracks and
exhaust gas leakage.
If any leak is found, take care to avoid getting
burned by exhaust gas.
Terminal Board
Содержание Maxi-Power MP65 T4F
Страница 65: ...N o t f o r R e p r o d u c t i o n 65 Dimensions units in...
Страница 66: ...N o t f o r R e p r o d u c t i o n 66 ALLMAND COM Dimensions units mm...
Страница 67: ...N o t f o r R e p r o d u c t i o n 67 Generator Wiring Diagram...
Страница 68: ...N o t f o r R e p r o d u c t i o n 68 ALLMAND COM Engine Wiring Diagram...
Страница 69: ...N o t f o r R e p r o d u c t i o n 69 Connector Terminal Arrangement...
Страница 71: ...N o t f o r R e p r o d u c t i o n 71 7 Specifications 7 2 Cooling Water Piping A180829E Engine...
Страница 74: ...N o t f o r R e p r o d u c t i o n 74 ALLMAND COM...
Страница 75: ...N o t f o r R e p r o d u c t i o n 75...
Страница 76: ...N o t f o r R e p r o d u c t i o n...