Periodic Inspection
60
Check Accumulations in Exhaust System
Every 250 Hours
When a diesel engine driven generator is continuously operated with less than 30% load or no load for a
long time, carbon will accumulate inside the exhaust pipes, exhaust muffler, and engine body. Unburned
fuel may also come out from connected portions of exhaust pipe and outlet port of the exhaust muffler. If it
is continuously operated under these conditions, the fuel which comes out could ignite and cause a fire.
Further, wet-stacking and carbon accumulation could cause power drop in the engine as well as
overheating, resulting in serious damage to the engine. If this occurs, eliminate the carbon accumulation by
burning it under full load operation (to increase exhaust heat) until the exhaust gas becomes almost clear.
(For load current, refer to the following table as a standard value.)
Frequency
Hz
60
Rated voltage
V
240
480
Load current
A
120
60
In case of load operation, increase load factor step by step while checking the condition of the exhaust.
Do not place flammables nearby because it could cause fire.
Check GFCI Receptacles
Every 1 months or every 250 hour
<Procedure>
1. Unplug all appliances from the generator.
2. Start the engine.
3. Turn [ON] the breaker on the instrument panel of this
machine.
4. Press the TEST BUTTON
The RESET BUTTON should extend with a click.
If the RESET BUTTON does not extend, contact your
nearest dealer.
5. Press the RESET BUTTON
6. When the RESET BUTTON extends during operation.
Unplug all appliances from the GFCI protected
receptacle.
Press the RESET BUTTON:
IF THE GFCI CANNOT BE RESET: The GFCI is faulty. Contact your nearest dealer.
IF THE GFCI RESETS PROPERLY: Check the appliance or the power cord.
If the generator is stored outdoors, unprotected from the weather, test the GFCI receptacle before each
use.
In case the GFCI has tripped due to the hazard of ground fault currents, investigate the cause and
correct it.
Test Button
Reset Button
Содержание Maxi-Power MP65 T4F
Страница 65: ...N o t f o r R e p r o d u c t i o n 65 Dimensions units in...
Страница 66: ...N o t f o r R e p r o d u c t i o n 66 ALLMAND COM Dimensions units mm...
Страница 67: ...N o t f o r R e p r o d u c t i o n 67 Generator Wiring Diagram...
Страница 68: ...N o t f o r R e p r o d u c t i o n 68 ALLMAND COM Engine Wiring Diagram...
Страница 69: ...N o t f o r R e p r o d u c t i o n 69 Connector Terminal Arrangement...
Страница 71: ...N o t f o r R e p r o d u c t i o n 71 7 Specifications 7 2 Cooling Water Piping A180829E Engine...
Страница 74: ...N o t f o r R e p r o d u c t i o n 74 ALLMAND COM...
Страница 75: ...N o t f o r R e p r o d u c t i o n 75...
Страница 76: ...N o t f o r R e p r o d u c t i o n...