QUICKDESIGNER
OMRON
••••
171
PLC Type
Select the PLC type from the list box.
(Omron Serial).
See PLC Type on page 5.
Port Button
Click the Port button to display the Serial Parameters dialog. The following settings are recommended
for
Omron (Serial)
. Note the setting differences for the C20H and C200H-LK201/202 Host Link
Adapters.
C20H C200H-LK201 HLA C200-LK202
Elect. Format
RS232C
RS232C
RS422/485 Full Duplex
Baud Rate
9600
19200
19200
Data Bits
7
8
8
Parity
Even
Even
Even
Stop Bits
2
1
1
Handshake
None
None
None
Protocol Button
The following drawing shows the Omron protocol setup dialog box. Enter the Default station ID (PLC
address). The default setting for Timeout and Number of retries is correct for most applications. Long
variables (L format qualifier) for 32-bit signed integer and Float (F format qualifier) for 32-bit IEEE
float variables can be read in reverse word order.
Click OK to return to the Project Setup dialog box.