248
Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
Chapter 9
Kinetix 5700 Safe Torque-off Function
Explicit Messages
You can use explicit messages to obtain additional diagnostic information from
the safety controller by using an MSG instruction.
Safety Supervisor State
The safety supervisor state provides information on the state of the integrated
safety connection and the mode of operation. There is only one safety
supervisor object per drive module. Therefore, for dual-axis inverters, the
safety supervisor is the same on both axes.
Table 124 - Safety Supervisor State: MSG
Table 125 - Safety Supervisor States
SafeTorqueOffDisableStatus
[4]
BOOL
Status of SI.TorqueDisabled
SafetyOutputConnectionClosed
[30]
BOOL
1 if all output connections are closed
SafetyOutputConnectionIdleStatus
[31]
BOOL
1 if safety controller is in program mode
AxisSafetyFaults
763
DINT
SafetyCoreFault
[1]
BOOL
Loss of communications to safety control
SafetyTorqueOffFault
[3]
BOOL
Status of SI.SafetyFault
(1) Bits not shown are always zero.
Table 123 - Safety Related Axis Tags (continued)
Logix Designer Tag Name
Attribute [bit]
Type
Description
Parameter
Value
Description
Service Code
0x0E
Get attribute single
Class
0x39
Safety supervisor
Instance
1
Attribute
0x0B
Device status
Data Type
SINT
Short integer
Value
Safety Supervisor State
Definition
Safety Mode
2
Configured (no safety connection)
No active connections
Integrated
4
Running
Normal running state
Integrated
7
Configuring
Transition state
Integrated
8
Not Configured
Hardwired STO mode with
torque disabled
Hardwired (out of the box)
51
Not Configured (torque permitted)
Hardwired STO mode with
torque permitted
Hardwired (out of the box)
52
Running (torque permitted)
STO bypass state
Integrated