124
Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
Chapter 5
Connect the Kinetix 5700 Drive System
Single-axis Inverter Shield Clamp Installation
Follow these steps to apply the single-axis inverter motor-cable shield clamp.
1.
Remove the larger (lower position) clamp or small (upper position)
clamp, depending on the power conductor size used in your application.
2.
Loosen the clamp screw.
3.
Position the exposed portion of the cable braid directly in line with the
clamp.
4.
Tighten the clamp screw.
Make sure the cable clamp tightens around the overall cable shield and
provides a good bond between the cable shield and the drive chassis.
Torque value 5.6 N•m (50 lb•in), max.
, 10 AWG (series A) cables are prepared per
, and series B cables do not require preparation.
Figure 80 - Single-axis Inverter Cable Installation (series A and B, 10 AWG cables)
5.
Repeat
through
for each drive in multi-axis configurations.
IMPORTANT
Make sure to use the proper size clamp depending on cable
diameter.
IMPORTANT
Make sure the clamp is aligned with the shield braid and not
heat shrink.
–
MBRK
+
Motor Cable
Shield Clamp
2198-KITCON-DSL
Motor Feedback
Connector Kit
Motor Power
(MP) Connector
Motor Brake
(BC) Connector
Clamp Screw
(M10)
2198-S
xxx
-ERS3
Single-axis Inverter
(front view)
Small Cable Clamp
Overall Cable Shield
Under Clamp
Motor Power Wires
Bulletin 2090-CPBM7DF
Power/Brake Cable
Small Cable Clamp
(10, 8, and 6 AWG)
Large Cable Clamp
(4 and 2 AWG)