Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
101
Connect the Kinetix 5700 Drive System
Chapter 5
Wiring Requirements
Wires must be copper with 75 °C (167 °F) minimum rating. Phasing of main
AC power is arbitrary and earth ground connection is required for safe and
proper operation.
Refer to
for interconnect diagrams.
Table 47 - DC-bus Power Supply Wiring Requirements
Table 48 - iTRAK Power Supply Wiring Requirements
IMPORTANT
The National Electrical Code and local electrical codes take precedence
over the values and methods provided.
DC-bus Power Supply
Cat. No.
Description
Connects to Terminals
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
Pin
Signal
2198-P031
2198-P070
Mains input
power
6…10
(10…8)
10.0 (0.39)
0.5…0.8
(4.4…7.1)
2198-P141
2198-P208
10…35
(8…2)
20.0 (0.79)
2.5…4.5
(22…40)
2198-P
xxx
PELV/SELV
24V power
(connector plug)
CP-1
CP-2
24V+
24V–
0.5…2.5
(20…14)
7.0 (0.28)
0.22…0.25
(1.9…2.2)
DC Bus power
Bus bar
DC–
DC+
N/A
(1)
N/A
N/A
Contactor enable
EN–
EN+
CONT EN–
CONT EN+
0.14…2.5
(26…12)
7.0 (0.28)
0.4…0.5
(3.5…4.4)
Shunt resistor
RC-1
RC-2
SH
DC+
1.5…6
(16…10)
12.0 (0.47)
0.5…0.6
(4.5…5.3
Digital inputs
IOD-1
IOD-2
IOD-3
IOD-4
IN1
COM
IN2
COM
0.14…1.5
(26…16)
10.0 (0.39)
N/A
(2)
(1) Shared DC-bus power connections are always made from one drive module to another over the bus-bar connection system. These terminals do not receive discrete wires.
(2) This connector uses spring tension to hold wires in place.
L3
L2
L1
L3
L2
L1
iTRAK Power Supply
Cat. No.
Description
Connects to Terminals
Wire Size
mm² (AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
Pin
Signal
2198T-W25K-ER
DC-bus input
power
Bus bar
DC–
DC+
N/A
(1)
N/A
N/A
SELV/PELV rated
24V power
(connector plug)
CP-1
CP-2
24V+
24V–
1.5…4
(2)
(16…12)
10.0 (0.39)
0.5…0.6
(4.4…5.3)
6
(10)
10.0 (0.39)
0.7…0.8
(3)
(6.1…7.0)
(1) Shared DC-bus power connections are always made from power supply to power supply over the bus-bar connection system. These terminals do not receive discrete wires.
(2) Use sufficient wire size to support the complete control power load, including the Kinetix 5700 drive modules and pass-through current for the attached motor modules.
(3) Depending on 24V current demand, 6 mm
2
(10 AWG) wire can be required. When 6 mm
2
(10 AWG) wire is used, these torque specifications apply.
TIP
For iTRAK power supply wiring requirements not shown here, see the iTRAK
System User Manual, publication