134
Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
Chapter 5
Connect the Kinetix 5700 Drive System
External Active-shunt
Connections
Active shunts are available from the Rockwell Automation® Encompass™
Partner Powerohm Resistors, Inc.
Active shunts wire to the DC-bus studs. The capacitor modules are equipped
with spacers that slide onto the M8 studs. When the system configuration
includes external DC-bus and active shunt connections, external DC-bus
connections are made below the spacer and active shunt connections are made
above the spacer.
Figure 90 - Active Shunt Connections
(1) A 2198-CAPMOD-2240 capacitor module is needed in systems with the external DC-bus current up to 100 A.
(2) A 2198-CAPMOD-DCBUS-IO extension module is needed if the external DC-bus current is greater than 100 A, up to a maximum
for example configurations that include these capacitor modules.
Table 77 - Active Shunts Compatible with Kinetix 5700 Drive Systems
Rockwell Automation
Encompass Partners
Contact Information
Powerohm Resistors, Inc.
5713 13th Street
Katy, Texas 77493
Tel: (800) 838-4694
2198-CAPMOD-2240
(1)
or
2198-CAPMOD-DCBUS-IO
(2)
Capacitor Module
(2198-CAPMOD-2240
module is shown)
Active Shunt
Lug Connections
(above spacer)
DC-Bus
Lug Connections
(below spacer)
Spacer
Rockwell Automation
Encompass Partners
Powerohm Cat. No.
(1)
(1) PKB
xxx
active shunt modules use built-in internal brake resistors. PWB
xxx
active shunt modules require appropriately sized
external brake resistors.
Power Rating
kW
Current Rating
Amps
Powerohm Resistors, Inc.
PKB005
1.5
N/A
PKB010
2.0
N/A
PKB050
7.0
N/A
PWB035
22.7
35
PWB110
71.5
110
ATTENTION:
Do not use Powerohm active-shunt modules at input line
voltages that exceed 500V AC. Active-shunt thermal-overload shutdown can
occur if input line voltage exceeds 500V AC.