Rockwell Automation Publication 5069-IN003C-EN-P - December 2016
5069 Compact I/O EtherNet/IP Adapters
WARNING:
Special Conditions for Safe Use:
• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (as defined in
EN/IEC 60529) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The
enclosure must be accessible only by the use of a tool.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated voltage when applied in
Zone 2 environments.
• The instructions in the user manual shall be observed.
• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this
product.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Earthing is accomplished through mounting of modules on rail.
• Devices shall be used in an environment of not more than Pollution Degree 2.
• The equipment must be used only with ATEX/IECEx certified Rockwell Automation backplanes.
• When installed in a non-hazardous area, the equipment may alternatively be installed in a controlled environment that provides equivalent protection.
• 5069-AEN2TR EtherNet/IP adapter only — The USB port is intended for temporary local programming purposes only and not intended for permanent
connection. Do not use the USB port in hazardous locations.
Prevent Electrostatic Discharge
ATTENTION:
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when
you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Electrical Safety Considerations
ATTENTION:
• SELV-listed supplies must be used for MOD and SA power if there are Functional Safety modules connected to the 5069 Compact I/O system.
• 5069-AEN2TR EtherNet/IP adapter only:
– Do not wire more than 1 conductor on any single RTB terminal.
• 5069-AENTR EtherNet/IP adapter only:
– All wiring must comply with applicable electrical installation requirements (e.g., N.E.C. article 501-4(b)).
– Wire conductor and insulation ratings shall support minimum temperature rating of 105 °C (221 °F).
– Do not wire more than 1 conductors on any single terminal.
ATTENTION:
• In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle the
module.
• This equipment is certified for use only within the surrounding air temperature range of 0…60 °C (32…140 °F) The equipment must not be used outside of
this range.
• Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
• 5069-AEN2TR EtherNet/IP adapter only — The USB port is intended for temporary local programming purposes only and not intended for permanent
connection. The USB cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.