Install the SA Power RTB
1. Hook the bottom of the SA power RTB on the adapter.
2. Push the RTB against the adapter until the RTB clicks
into place.
3. Push the RTB handle against the RTB until you hear another
click.
Connect SA DC Power to the 5069-AEN2TR Adapter
Before you connect an external DC power source to the SA power
RTB, make sure that the SA power source is properly sized. For
example, if the total SA power current draw is 7 A, you can use an SA
power supply that is limited to 7 A.
1. Confirm that MOD power and all sources of SA power are
turned off.
2. Strip insulation from the wires that you connect to the RTB.
3. Connect the DC(+) wire from the external DC power supply
to the first + terminal.
4. Connect the DC(—) wire from the external SA DC power
supply to the first — terminal.
5. Connect a wire from an earth ground location to the
first
terminal on the RTB. The earth ground location can
be the external SA power supply, the DIN rail, or other earth
ground location.
WARNING:
If you connect or disconnect the Removable Terminal
Block (RTB) with power applied, an Electric Arc can occur. This
could cause an explosion in hazardous location installations.
The Removable Terminal Block (RTB) does not support "Removal
and Insertion Under Power" (RIUP) capability. Do not connect or
disconnect the Removable Terminal Block (RTB) while power is
applied. Be sure that power is removed before proceeding.
IMPORTANT
The SA Power RTB is used only on the 5069-AEN2TR adapter.
WARNING:
If you connect or disconnect wiring while the field-
side power is on, an electric arc can occur. This could cause an
explosion in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
RTB Type
Action
Screw
Strip12 mm (0.47 in.) of insulation from the wires.
Spring
Strip 10 mm (0.39 in.) of insulation from the wires.
ADAPTER
COMPACT 5000
AENTR
Compact I/O
Compact I/O
™
5069-AEN2TR
SA Power RTB
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
5069-RTB6-SPRING RTB
5069-RTB6-SCREW RTB
5069-RTB6-SPRING RTB
5069-RTB6-SCREW RTB
5069-RTB6-SPRING RTB
5069-RTB6-SCREW RTB