Rockwell Automation Publication 5069-IN003C-EN-P - December 2016

5069 Compact I/O EtherNet/IP Adapters

Connect the Adapter to an EtherNet/IP Network

Use an RJ45 straight cable to connect the adapter to an EtherNet/IP 
network.

1. If needed, wire the RJ45 connector as shown.

2. Connect the RJ45 cable to an Ethernet port on the bottom of 

the adapter. You can connect two RJ45 cables to the adapter.

Install 5069 Compact I/O Modules

Install 5069 Compact I/O modules on the right side of the adapter. 

If the end cap is installed on the adapter, you must remove it before you 
can install the I/O modules.

For more information on how to install 5069 Compact I/O modules, 
see the installation instructions available with each 5069 Compact I/O 
module catalog number.

Install the End Cap

A 5069-ECR end cap is shipped with the adapter.

You must install an end cap on the right side of the last module in a 
5069 Compact I/O system. The end cap covers the exposed 
interconnections on the last module in the system. If you do not install 
the end cap before powering the system, equipment damage or injury 
from electric shock can result.

If the end cap is not installed and you have installed all required 
modules in the system, install the end cap.

1. Align the end cap with interlocking pieces on the adapter.

2. Push the end cap toward the DIN rail until it locks into place.

Power the System

After the end cap is installed on the last module in the system, turn on 
power to the MOD power RTB and the SA power RTB.

WARNING: 

If you connect or disconnect the communication 

cable with power applied to this module or any device on the 
network, an electric arc can occur. This could cause an explosion 
in hazardous location installations.

Be sure that power is removed or the area is nonhazardous 
before proceeding.

This warning applies to connections to ports 1 and 2 on both 

adapters. For more information on where the ports are located 
on the adapter, see 

About the Adapters on page 5

.

Connector 
Number

Color

1585J 8-pin 
Cables with 
Support for 10/
100/1000 Mbps

1585J 8-pin 
Cables with 
Support for 10/
100 Mbps

1585J 4-pin 
Cables with 
Support for 10/
100 Mbps

1

White/

Orange

BI_DA+

2

Orange

BI_DA-

TxData -

3

White/

Green

BI_DB+

Recv Data +

4

Blue

BI_DC+

Unused

N/A

5

White/Blue

BI_DC-

Unused

N/A

6

Green

BI_DB-

Recv Data -

7

White/

Brown

BI_DD+

Unused

N/A

8

Brown

BI_DD-

Unused

N/A

ADAPTER

COMPACT 5000

AENTR

5069-AEN2T

R

Compact I/O

Compact I/O

Top 

Interlocking 
Pieces

End Cap

Bottom 
Interlocking 
Pieces

Top 

Interlocking 
Pieces

End Cap

Bottom 
Interlocking 
Pieces

5069-AEN2TR 
Adapter

5069-AENTR 
Adapter

Содержание Compact I/O 5069 series

Страница 1: ...tion on how to use 5069 Compact I O EtherNet IP adapters including the compatible Logix5000 controllers and Logix Designer application versions see the publications that are listed in Additional Resources on page 19 SummaryofChanges This publication was revised to include information about the 5069 AENTR adapter Topic Page Summary of Changes 1 About the Adapters 5 Install a 5069 Compact I O System...

Страница 2: ...e code de pratique en vigueur Si cet équipement est utilisé d une façon qui n a pas été définie par le fabricant la protection fournie par l équipement peut être compromise 㭒㦮 a G㩲䛞G 䂮 SG 㩫 SG㧧 G G㥶㰖G 㑮䞮 G㩚㠦G Gⶎ G䙂䞾䞮㡂G 䂮 SG 㩫G G㧧 㠦Gὖ䞲G㺎ἶG㧦 G 㦮Gⶎ 㦚G 㔲G㧓ἶG㑯㰖䞮 㕃㔲㡺 UG 㣿㧦 G Gὖ G 㩫 SG G G䚲㭖㠦 G㣪ῂ䞮 G 䟃㠦G 䟊G 㔲G 䂮G G G㰖䂾㦚G㑯㰖䟊㟒G䞿 U 䂮 SG㫆㩫 SGṖ SG 㣿 SG㫆Ⱃ SG 䟊 SG㥶㰖 㑮G G G㧧㠛㦖Gὖ G 㩫㠦G G㩗㩞䞲Gᾦ㥷㦚G 㦖G 㣿㧦 G䐋䟊 ⰢG㑮䟟䟊㟒G䞿...

Страница 3: ...r les autorités locales qualifiées au moment de l installation WARNING EXPLOSION HAZARD Donotdisconnectequipmentunlesspowerhasbeenremovedortheareais known to be nonhazardous Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous Secure any external connections that mate to this equipment by using screws sliding latches threaded connect...

Страница 4: ...mming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations Prevent Electrostatic Discharge ATTENTION Thisequipmentissensitivetoelectrostaticdischarge whichcancauseinternaldamageandaffectnormaloperation Followtheseguidelineswhen you handle this equipment Touch a grounded object to discharge potential static Wear an approved grounding wriststrap Do n...

Страница 5: ...ations Besurethat power is removed or the area is nonhazardous before proceeding WARNING Do not use the USB port in hazardous locations 5069 AEN2TR EtherNet IP adapter only IMPORTANT Any illustrations charts sample programs and layout examples shown in this publication are intended solely for the purposes of example Since there are many variables and requirements associated with any particular ins...

Страница 6: ...NG kit contains the 5069 RTB5 SPRING RTBs We recommend that you order only the RTB type that your system requires External power supply for Module MOD Power A power supply that is adequately sized to provide MOD power that is system side power to the 5069 Compact I O system For more information see System Power Considerations on page 8 External power supply for Sensor Actuator SA Power A power sup...

Страница 7: ...in 130 31 mm 5 13 in 101 66 mm 4 00 in ATTENTION This product is grounded through the DIN rail to chassis ground Use zinc plated chromate passivated steel DIN rail to assure proper grounding The use of other DIN rail materials for example aluminum or plastic that can corrode oxidize or are poor conductors can result in improper or intermittent grounding Secure DIN rail to mounting surface approxim...

Страница 8: ...9CompactI Osystem MOD power is provided through the MOD power RTB and passed across the MOD power bus You must limit the MOD power source to 10 A max at 18 32V DC Confirm that the external MOD power supply is adequately sized for the total MOD power bus current draw in the system Forexample ifthetotalMODpowercurrentdraw includingcurrentinrush requirements is5A youcanuseaMODpowersupplythatislimited...

Страница 9: ... 3 Position the adapter so that the back of it faces the DIN rail 4 Press the adapter against the DIN rail until you hear a click 5 Confirm that the adapter is latched securely ConnectPowertothe5069 AEN2TRAdapter Before you connect MOD power or SA power to a 5069 AEN2TR adapter complete the following tasks Read System Power Considerations on page 8 Confirm that the external power supplies that sup...

Страница 10: ...Power RTB is used only on the 5069 AEN2TR adapter IMPORTANT Your application can require a power control device for example a switch between the external 24V DC power source and the adapter to control when the module is powered If so you must install the power control device at theVDC terminal on the removable terminal block If you install the power control device at theVDC terminal the adapter ca...

Страница 11: ...t connect or disconnect the RemovableTerminal Block RTB while power is applied Be sure that power is removed before proceeding IMPORTANT The SA Power RTB is used only on the 5069 AEN2TR adapter WARNING If you connect or disconnect wiring while the field side power is on an electric arc can occur This could cause an explosioninhazardouslocationinstallations Besurethatpoweris removed or the area is ...

Страница 12: ... cause an explosioninhazardouslocationinstallations Besurethatpoweris removed or the area is nonhazardous before proceeding RTBType Action Screw Strip12 mm 0 47 in of insulation from the wires Spring Strip 10 mm 0 39 in of insulation from the wires RTBType Action Screw 1 Insert the wire into the terminal 2 Turn the screwdriver to close the terminal on the wire Torque the screw to 0 4 N m 3 5 lb in...

Страница 13: ...ty Do not connect or disconnect the RemovableTerminal Block RTB while power is applied Be sure that power is removed before proceeding IMPORTANT The Power RTB is used only on the 5069 AENTR adapter MOD POWER SA POWER ADAPTER 5069 AENTR 2 1 Compact I O OK NET LINK 1 LINK 2 WARNING EXPLOSION HAZARD Do Not Disconnect While Circuit is Live Unless Area Is Known To Be Non Hazardous A VERTISSEMENT RISQUE...

Страница 14: ...eeding RTBType Action Screw Strip 10 mm 0 39 in of insulation from the wires Spring Strip 10 mm 0 39 in of insulation from the wires RTBType Action Screw 1 Insert the wire into the terminal 2 Turn the screwdriver to close the terminal on the wire Torque the screw to 0 5 0 6 N m 4 4 5 3 lb in Spring Push the wire into the terminal If the wire is too thin crimp a wire ferrule on the wire and insert ...

Страница 15: ...river to close the terminal on the wire Torque the screw to 0 5 0 6 N m 4 4 5 3 lb in Spring Push the wire into the terminal If the wire is too thin crimp a wire ferrule on the wire and insert it RTBType Action Screw 1 Insert the wire into the terminal 2 Turn the screwdriver to close the terminal on the wire Torque the screw to 0 5 0 6 N m 4 4 5 3 lb in Spring Push the wire into the terminal If th...

Страница 16: ...odules in the system install the end cap 1 Align the end cap with interlocking pieces on the adapter 2 Push the end cap toward the DIN rail until it locks into place PowertheSystem After the end cap is installed on the last module in the system turn on power to the MOD power RTB and the SA power RTB WARNING If you connect or disconnect the communication cable with power applied to this module or a...

Страница 17: ...onnect the module while power is applied Be sure that power is removed before proceeding IMPORTANT When you remove MOD power from a 5069 Compact I O EtherNet IP adapter you shut down power to all modules in the 5069 Compact I O system That is all system side is removed When you remove SA power from the 5069 Compact I O EtherNet IP adapter all field side power that is provided by the adapter is rem...

Страница 18: ...tinuous Basic InsulationType SA and MOD Power to Backplane 300V continuous Basic InsulationType SA to MOD Power 300V continuous Basic InsulationType Ethernet to Backplane Type tested at 1500V AC for 60 s 300V continuous Double InsulationType Ethernet to MOD Power 300V continuous Double InsulationType Ethernet to SA Power Type tested at 4242V DC for 60 s No isolation between Ethernet ports Recommen...

Страница 19: ...ion ENET RM002 Describes how to use EtherNet IP adapters with Logix5000 controllers and communicate with other devices on the EtherNet IP network EtherNet IP Embedded SwitchTechnology Application Guide publication ENET AP005 Describes how to install configure and maintain linear and Device Level Ring DLR networks by using Allen Bradley EtherNet IP devices that are equipped with embedded switch tec...

Страница 20: ...ve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pdf Technical Support Center Knowledgebase Articles How toVideos FAQs Chat User Forums and Product Notification Updates https rockwellautomation custhelp com LocalTechnical Suppo...

Отзывы: