18
Rockwell Automation Publication 5069-IN003C-EN-P - December 2016
5069 Compact I/O EtherNet/IP Adapters
Specifications
This table includes a subset of specifications for the adapter. For full specifications, see the 5069 Compact I/O Modules Specifications Technical
Data, publication
5069-TD001
.
Attribute
5069-AEN2TR
5069-AENTR
Temperature, operating
• IEC 60068-2-1 (Test Ad, Operating Cold)
• IEC 60068-2-2 (Test Bd, Operating Dry Heat)
• IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0 °C < Ta < +60 °C
(+32 °F < Ta < +140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Enclosure type rating
None (open-style)
Voltage and current ratings
MOD Power
450 mA @ 18…32V DC
220 mA @ 18…32V DC
MOD Power Inrush
850 mA for 125 ms
1750 mA for 70 ms
SA Power
10 mA @ 0…32V DC
25 mA @ 0…240V AC, 47…63 Hz
ATEX/IECEx, 125V AC Max
5 mA @ 0…32V DC
2 mA @ 0…240V AC, 47…63 Hz
MOD Power (Passthrough)
9.55 A @ 18…32V DC
9.78 A @ 18…32V DC
SA Power (Passthrough)
9.95 A @ 0…32V DC
9.975 A @ 0…240V AC, 47…63 Hz
ATEX/IECEx, 125V AC Max
Do not exceed 10 A current draw at the MOD or SA Power RTB.
9.95 A @ 0…32V DC
9.975 A @ 0…240V AC, 47…63 Hz
Do not exceed 10 A current draw at the MOD or SA Power RTB.
Isolation voltage
300V (continuous), Basic Insulation Type, SA, and MOD Power
to Backplane
300V (continuous), Basic Insulation Type, SA to MOD Power
300V (continuous), Basic Insulation Type, Ethernet to Backplane
300V (continuous), Double Insulation Type, Ethernet to
MOD Power
300V (continuous), Double Insulation Type, Ethernet to SA Power
50V (continuous), Functional Insulation Type, Ethernet to USB
300V (continuous), Basic Insulation Type, USB to Backplane
300V (continuous), Double Insulation Type, USB to MOD Power
300V (continuous), Double Insulation Type, USB to SA Power
No isolation between Ethernet ports
Type tested at 1500V AC for 60 s
300V (continuous), Basic Insulation Type, SA, and MOD Power
to Backplane
300V (continuous), Basic Insulation Type, SA to MOD Power
300V (continuous), Basic Insulation Type, Ethernet to Backplane
Type tested at 1500V AC for 60 s
300V (continuous), Double Insulation Type, Ethernet to
MOD Power
300V (continuous), Double Insulation Type, Ethernet to SA Power
Type tested at 4242V DC for 60 s
No isolation between Ethernet ports
Recommended external overcurrent protection
N/A
MOD Power: 10…12A @ 22.5…43.2 A2t, Fast Acting
SA Power: 20 A @ 250V AC
Wire size
5069-RTB4-SCREW, 5069-RTB6-SCREW connections:
0.5…1.5 mm
2
(22…16 AWG) solid or stranded copper wire
rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max
diameter including insulation, single wire connection only.
5069-RTB4-SPRING, 5069-RTB6-SPRING connections:
0.5…1.5 mm
2
(22…16 AWG) solid or stranded copper wire
rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max
diameter including insulation, single wire connection only.
Ethernet connections: Ethernet Cabling and Installation
according to IEC 61918 and IEC 61784-5-2.
0.25…2.5 mm
2
(22…14 AWG) solid or stranded copper wire
rated at 105 °C (221 °F), or greater, 1.2 mm (3/64 in.) insulation
m, single wire connection only.
Grounding: 2.5 mm
2
(14 AWG) solid or stranded copper wire
rated at 105 °C (221 °F), or greater, 3.5mm (0.14in) max
diameter including insulation, single wire connection only.
Ethernet connections: Ethernet Cabling and Installation
according to IEC 61918 and IEC 61784-5-2.
Insulation stripping length
5069-RTB4-SCREW, 5069-RTB6-SCREW connections:
12 mm (0.47 in.)
5069-RTB4-SPRING, 5069-RTB6-SPRING connections:
10 mm (0.39 in.)
5069-RTB5-SCREW connections: 10 mm (0.39 in.)
5069-RTB5-SPRING connections: 10 mm (0.39 in.)
Terminal block torque specifications
5069-RTB4-SCREW and 5069-RTB6-SCREW: 0.4 N•m (3.5 lb•in)
5069-RTB4-SPRING and 5069-RTB6-SPRING: Not applicable
5069-RTB5-SCREW: 0.5…0.6 N•m (4.4…5.3 lb•in)
5069-RTB5-SPRING: Not applicable
North American Temp Code
T4
ATEX Temp Code
T4
IECEx Temp Code
T4