5069 Compact I/O EtherNet/IP Adapters
Remove or Replace the Adapter
1. Turn off power to the MOD power RTB and, if used, the SA
power RTB.
2. Disconnect wires from the RTBs. For more information, see
Disconnect Wires from RTBs on page 15
.
3. Remove the RTBs:
– 5069-AEN2TR adapter - Pull the RTB handles to remove
the MOD power RTB and SA power RTB.
– 5069-AENTR adapter - Hold the top and bottom of the
RTB and pull the RTB off the adapter.
4. Remove the EtherNet/IP cable from the adapter.
5. Push down on the front of the DIN rail latches. A click
indicates that the DIN rail latches are open.
If the DIN rail latches fail to remain in the open position, hold
them down.
6. Pull the adapter off the DIN rail.
7. Repeat the installation steps that are described beginning at
Set
the Network Internet Protocol (IP) Address on page 8
.
8. Apply MOD power and, if necessary, SA power to the system.
ATTENTION:
Do not remove or replace an adapter while power is
applied. Interruption of the backplane can result in unintentional
operation or machine motion.
WARNING:
If you insert or remove the Adapter Module while
power is on, an electric arc can occur. This could cause an
explosion in hazardous location installations. The module does
not support "Removal and Insertion Under Power" (RIUP)
capability. Do not connect or disconnect the module while power
is applied. Be sure that power is removed before proceeding.
IMPORTANT
When you remove MOD power from a 5069 Compact I/O
EtherNet/IP adapter, you shut down power to all modules in
the 5069 Compact I/O system. That is, all system-side is
removed. When you remove SA power from the 5069
Compact I/O EtherNet/IP adapter, all field-side power that is
provided by the adapter is removed. If the system uses the SA
power provided by the SA power RTB on a 5069-FPD field
potential distributor, the system does not lose field-side
power to the right of the field potential distributor.
In this case, you must use a separate power source for the SA
power RTB on the field potential distributor.
We strongly recommend that you take the appropriate actions
to help prevent unintended consequences that can result
from a system power shutdown before removing MOD power
or SA power from the adapter or field potential distributor.
Despite the removal of field-side power from SA RTBs on the
adapter or field potential distributor, the 5069-OB16 and
5069-OB16F modules continue to receive field-side power
from an external power source connected to the LA (+) and
LA (–) terminals on the modules.
ATTENTION:
Do not remove or replace a Terminal Base
unit while power is applied. Interruption of the
backplane can result in unintentional operation or
machine motion.