10
Rockwell Automation Publication 5069-IN003C-EN-P - December 2016
5069 Compact I/O EtherNet/IP Adapters
Install the MOD Power RTB
1. Hook the bottom of the MOD power RTB on the adapter.
2. Push the RTB against the adapter until the RTB clicks into
place.
.
3. Push the RTB handle against the RTB until you hear another
click.
Connect MOD Power to the 5069-AEN2TR Adapter
Before you connect an external power source to the MOD power RTB,
make sure that the MOD power source is properly sized. For example,
if the total MOD power current draw is 4 A, you can use a MOD
power supply that is limited to 4 A.
1. Verify that the external power supply is not powered.
2. Strip insulation from the wires that you connect to the RTB.
3. Connect the 24V DC(+) wire from the external power supply
to the first + terminal.
4. Connect the 24V DC(—) wire from the external power supply
to the first — terminal.
WARNING:
If you connect or disconnect the Removable Terminal
Block (RTB) with power applied, an Electric Arc can occur. This
could cause an explosion in hazardous location installations.
The Removable Terminal Block (RTB) does not support "Removal
and Insertion Under Power" (RIUP) capability. Do not connect or
disconnect the Removable Terminal Block (RTB) while power is
applied. Be sure that power is removed before proceeding.
IMPORTANT
The MOD Power RTB is used only on the 5069-AEN2TR
adapter.
IMPORTANT
Your application can require a power control device, for
example, a switch, between the external 24V DC power
source and the adapter to control when the module is
powered. If so, you must install the power control device at
the VDC+ terminal on the removable terminal block.
If you install the power control device at the VDC- terminal,
the adapter can fail to power up or power down properly.
WARNING:
If you connect or disconnect wiring while the field-
side power is on, an electric arc can occur. This could cause an
explosion in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
ADAPTER
COMPACT 5000
AENTR
Compact I/O
Compact I/O
™
5069-AEN2TR
MOD Power RTB
RTB Type
Action
Screw
Strip12 mm (0.47 in.) of insulation from the wires.
Spring
Strip 10 mm (0.39 in.) of insulation from the wires.
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
5069-RTB4-SPRING RTB
5069-RTB4-SCREW RTB
5069-RTB4-SPRING RTB
5069-RTB4-SCREW RTB