5069 Compact I/O EtherNet/IP Adapters
Connect SA AC Power to the 5069-AEN2TR Adapter
Before you connect an external AC power source to the SA power
RTB, make sure that the SA power source is properly sized. For
example, if the total SA power current draw is 7 A, you can use an SA
power supply that is limited to 7 A.
1. Verify that the SA power source is not powered on.
2. Strip insulation from the wires that you connect to the RTB.
3. Connect the L1/AC(+) wire from the external SA AC power
source to the first + terminal.
4. Connect the L2/N/AC(—) wire from the external SA AC
power source to the first — terminal.
5. Connect a wire from an earth ground location to the
first
terminal on the RTB. The earth ground location can
be the external SA power supply, the DIN rail, or other earth
ground location.
TIP
The
symbol denotes an earth ground terminal that
provides a low impedance path between electrical circuits and
earth for functional purposes and provides noise immunity
improvement. This connection must be made for functional
purposes.
WARNING:
If you connect or disconnect wiring while the field-
side power is on, an electric arc can occur. This could cause an
explosion in hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
RTB Type
Action
Screw
Strip12 mm (0.47 in.) of insulation from the wires.
Spring
Strip 10 mm (0.39 in.) of insulation from the wires.
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
5069-RTB6-SPRING RTB
5069-RTB6-SCREW RTB
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
RTB Type
Action
Screw
1. Insert the wire into the terminal.
2. Turn the screwdriver to close the terminal on the wire. Torque the
screw to 0.4 N•m (3.5 lb•in).
Spring
Push the wire into the terminal.
If the wire is too thin, crimp a wire ferrule on the wire and insert it.
TIP
The
symbol denotes an earth ground terminal that
provides a low impedance path between electrical circuits and
earth for functional purposes and provides noise immunity
improvement. This connection must be made for functional
purposes.
5069-RTB6-SPRING RTB
5069-RTB6-SCREW RTB
5069-RTB6-SPRING RTB
5069-RTB6-SCREW RTB