Rockwell Automation Publication 2094-IN005H-EN-P - October 2012
40
Line Interface Module
Configure Branch-circuit Protection
Branch-circuit protection for the line interface module is customer configurable.
By moving the CB2/CB3 wiring harness (P4) from one side of CB1 to the other,
you can change the module operation. To understand this option, see the
simplified block diagram and table below.
Figure 35 - Simplified Block Diagram (catalog numbers 2094-AL
xx
S and 2094-BL
xx
S)
Figure 36 - Branch-circuit Operation (catalog numbers 2094-AL
xx
S and 2094-BL
xx
S)
Follow these steps to move the CB2/CB3 wiring harness to the optional
configuration.
1.
Remove all input power from the line interface module.
P4
J4
J4_B
Default Connection
(before CB1)
Circuit Breaker
(CB3)
Circuit Breaker
(CB1)
Circuit Breaker
(CB2)
Fuse Block
Disconnect
(140U-H-RM12B)
Safety Contactor
3-phase
Input (OPL)
Aux Power
Output (P1L)
24V DC
Aux Power
Output (P2L)
230V AC
I/O Power
Output (IOL)
24V DC
Control Power
Output (CPL)
230V AC
3-phase Power
Output (OPL)
to Drive
Transformer
(460V only)
Line Interface
Module
Optional Connection
(after CB1)
Cat. No.
Branch-circuit Protection Configurations
Module Operation
•
2094-AL15S, 2094-AL25S, 2094-AL50S,
2094-AL75S
(1)
(230V) line interface modules
•
2094-BL10S, 2094-BL25S, 2094-BL50S,
2094-BL75S
(1)
(460V) line interface modules
Input VAC to CB2 and CB3 before CB1
(default configuration)
Closing CB1 removes 3-phase power to the device (servo
drive), however 24V DC (CB2) and 230V AC (CB3) auxiliary
circuits remain energized.
Input VAC to CB2 and CB3 after CB1
(optional configuration)
Closing CB1 removes all power to the line interface module.
(1) Applies to 2094-AL
xx
S and 2094-BL
xx
S (series B) line interface modules only.
IMPORTANT
For the input VAC to CB2/CB3 before CB1 (default) configuration, no action is required.
ATTENTION:
To avoid shock hazard or personal injury, verify that all power has
been removed before proceeding. This system may have multiple sources of
power. Multiple disconnect switches may be required to de-energize the
system.