Rockwell Automation Publication 2094-IN005H-EN-P - October 2012
6
Line Interface Module
Establishing Noise Zones
Observe these guidelines when a 2094-AL
xx
S, 2094-BL
xx
S, or 2094-XL75S-C
x
line interface module is used in the system and mounted left of the drive with the
AC (EMC) line filter mounted above the module:
•
The clean zone (C) is to the right and beneath the drive system (gray
wireway).
•
The dirty zone (D) is to the left and above the drive system, and above and
below the line interface module (black wireway).
•
The very dirty zone (VD) is from the filter output to drive. Shielded cable
is required on the EMC filter (LOAD side) and the braided shield
attached to the clamp (when provided).
•
The sercos fiber-optic cables are immune to electrical noise.
Figure 3 - Establishing Noise Zones (EMC filter above the line interface module)
(1) If drive system I/O cable contains (dirty) relay wires, route cable with module I/O cable in dirty wireway.
(2) When space does not permit the 150 mm (6.0 in.) segregation, use a grounded steel shield instead. For examples, see the System
Design for Control of Electrical Noise Reference Manual, publication
GMC-RM001
.
(3) The Kinetix® 6000 drive is shown as an example of any drive or other device in configuration with the line interface module;
however, noise zones of other products will vary.
C
D
VD
D
D
D
D
D
D
VD
D
MAIN VAC
Line Interface Module
(catalog number
2094-AL
xx
S is shown)
Drive/
System Module
(3)
Dirty Wireway
Clean Wireway
I/O
(1)
and
Feedback Cables
No sensitive
equipment within 150
mm (6.0 in.)
(2)
Motor Power Cables
Very dirty Filter/Drive connections
segregated (not in wireway)
Route 24V DC I/O
Shielded Cable
Route Encoder/Analog/Registration
Shielded Cables
VAC LOAD
VAC LINE
AC Line Filter