Rockwell Automation Publication 2094-IN005H-EN-P - October 2012
32
Line Interface Module
Figure 28 - Wiring Requirements
(catalog numbers 2094-AL09 and 2094-BL02)
Cat. No.
Description
Connects to Terminals
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
Pin
Signal
2094-AL09
(230V)
VAC LINE
IPL-1
IPL-2
IPL-3
IPL-4
2.5
(14)
10.0
(0.38)
0.5…0.6
(4.4…5.3)
VAC LOAD
OPL-4
OPL-3
OPL-2
OPL-1
2094-BL02
(460V)
VAC LINE
IPL-4
IPL-3
IPL-2
IPL-1
4.0
(12)
10.0
(0.38)
1.5…1.8
(13.2…15.9)
VAC LOAD
OPL-1
OPL-2
OPL-3
OPL-4
Common
(230V or 460V)
Control power output
CPL-2
CPL-1
L1
L2/N
2.5
(14)
10.0
(0.38)
0.5…0.6
(4.4…5.3)
Brake and I/O power
output
PSL-1
PSL-2
PSL-3
PSL-4
MBRK PWR
MBRK COM
MBRK PWR
MBRK COM
L3
L2
L1
L3’
L2’
L1’
L3
L2
L1
L3’
L2’
L1’
ATTENTION:
To avoid hazard of electrical shock, complete the wiring of your module
before applying power. Once power is applied, connector terminals may have voltage
present even when not in use.
ATTENTION:
The input power for Bulletin 2094 line interface modules must come from
a grounded configuration. When an ungrounded power configuration is used, phases
L1, L2, and L3 (without a reference to earth ground) can drift and stress the line-filter
components internal to the line interface module.
ATTENTION:
Your Bulletin 2093, 2094, and 2099 servo drive user manual includes
examples of grounded and ungrounded power configurations. See
Additional
Resources
on
page 56
for publication numbers.