3–26
Regenerative Brake Operation
Control and Signal Wiring
Interlocking 1336 REGEN Enable with AC Drive Enable
It may be desirable to interlock the 1336 REGEN Enable Output
with the Enable Input on the connected 1336 PLUS, 1336 PLUS
II
,
1336 IMPACT or 1336 FORCE AC drive. This will keep the AC
drive from starting if the 1336 REGEN Converter is not enabled,
and will also remove the Enable signal from the AC drive if the
1336 REGEN Converter is faulted. If the Enable signals are not
interlocked, the AC drive may fault on bus overvoltage when
attempting to regenerate.
120V AC (High)
Connect to TB3-30 of 1336-L6, L6E, or L9E
on 1336 PLUS, PLUSII, IMPACT, or FORCE
AC Drive. 120V AC (RTN) connects to TB3-21,
25, or 29.
ENABLE RELAY
5
4
3
2
1
6
J16
FAULT RELAY
+24V DC
Connect to TB3-30 of 1336-L5, L5E, or L8E
on 1336 PLUS, PLUSII, IMPACT, or FORCE
AC Drive. 24V DC common connects to TB3-21,
25, or 29.
ENABLE RELAY
5
4
3
2
1
6
J16
FAULT RELAY
24V DC Operation
120V AC Operation