B–2
Specifications
Protection
AC Input Overvoltage Trip
Factory Set to +15% of Nominal Line
Voltage
Heatsink Over Temperature Trip
100˚C
1336R Converter Overcurrent Trip
Software Overcurrent Limit
Factory Set to 192% of AC Input Current
Hardware Overcurrent Limit
Factory Set to 245% of AC Input Current
Line Transients
Up to 6000 Volts Peak per ANSI C62.41-1991
Control Logic Noise Immunity
Showering Arc Transients Up to 1500 Volts Peak
Power Ride-Thru
6 mSec. at Full Load
Control Logic Ride-Thru
0.5 Sec. Minimum, 2 Sec. Typical
Regenerative DC Bus Supply Mode
Only
380VAC Input
480VAC Input
Bus Overvoltage Trip
670VDC
850VDC
Bus Undervoltage Trip
430VDC
520VDC
Nominal Bus Voltage
610VDC
735VDC