3–16
Regenerative Brake Operation
380-480VAC Power
Wiring
380-480VAC Power Connection Specifications
1. Use 75ºC Copper Wire Only.
2. Listed wires sizes are maximum/minimum wire sizes that the
terminals will accept — Not recommendations.
3. Input power connections to D frame Precharge Units and
input/output power connections to D frame Converters are
stud type terminations or bus bar bolts that require the use of
lug type connectors to terminate field installed conductors.
Lugs used with these connections are listed below.
1336 REGEN PRECHARGE UNIT
RATING
MAX/MIN WIRE SIZE
mm
2
(AWG)
MAX TORQUE
N-m (lb-in)
B Frame
13.3/0.5 (6/20) — Single Conductor
1.70 (15)
C Frame
26.7/0.8 (3/18) — Single Conductor
5.65 (50)
D Frame
127.0/2.1 (250MCM/14) — Single Conductor
67.4/2.1 (00/14) — Double Conductor
6.00 (52)
1321 3% LINE REACTOR CAT. NO.
MAX/MIN WIRE SIZE
mm
2
(AWG)
MAX TORQUE
N-m (lb-in)
-3R55-B and -3RA55-B
13.3/0.5 (6/20) — Single Conductor
1.70 (15)
-3R100-B and -3RA100-B
26.7/0.8 (3/18) — Single Conductor
5.65 (50)
-3R200-B and -3RA200-B
127.0/2.1 (250MCM/14) — Single Conductor
67.4/2.1 (00/14) — Double Conductor
6.00 (52)
1336 REGEN CONVERTER RATING
MAX/MIN WIRE SIZE
mm
2
(AWG)
MAX TORQUE
N-m (lb-in)
B Frame
13.3/0.5 (6/20) — Single Conductor
1.70 (15)
C Frame
26.7/0.8 (3/18) — Single Conductor
5.65 (50)
D Frame
127.0/2.1 (250MCM/14) — Single Conductor
67.4/2.1 (00/14) — Double Conductor
6.00 (52)
Catalog Number
PRECHARGE INPUT R, S, T
&
PE
CONVERTER INPUT R2, S2, T2
&
PE
CONVERTER OUTPUT DC+
&
DC–
T
&
B
Part Number
➊
Cable (per phase)
Qty. mm
2
(AWG)
Qty. P/N
1336R-VB180
(1)
107.2 (4/0)
(10) 54168
➋
➊
T & B COLOR-KEYED
®
Connectors require T & B WT117 or TBM-6 Crimper tool or equivalent. Lugs should be crimped
according to manufacturer’s tool instructions.
➋
5/16” stud. All other termination studs are 3/8”.