DC UPS
Subgroup 3 – DC UPS input Parameters
Subgroup 4 – Temperature parameters
OID
Description
Type
Parameters
Access
.1.3.6.1.4.1.49136.1.3.1.0
Power status, whether AC
power is on or not
All
0 - no, 1 - yes
Read-only
.1.3.6.1.4.1.49136.1.3.2.0
Indicates whether there
was a power outage in the
last 10 minutes
.1.3.6.1.4.1.49136.1.3.3.0
Indicates whether the
battery connected
to the DC UPS is being
charged
.1.3.6.1.4.1.49136.1.3.4.0
Indicates whether the
battery connected
to the DC UPS is being
discharged
.1.3.6.1.4.1.49136.1.3.5.0
Indicates general overload
at DC UPS. Occurs when
the DC UPS is operating at
a power above the
specified
All
0 - normal, 1 -
overheating
Read-only
.1.3.6.1.4.1.49136.1.3.6.0
Indicates general overload
at DC UPS. Occurs when
the DC UPS is operating at
a power above the
specified
All
0 - normal, 1 - overload
Read-only
.1.3.6.1.4.1.49136.1.3.7.0
Indicates malfunction of
indoor fan A at DC UPS
All
0 - normal, 1 - fail
Read-only
.1.3.6.1.4.1.49136.1.3.8.0
Indicates malfunction of
indoor fan B at DC UPS
All
0 - normal, 1 - fail
Read-only
.1.3.6.1.4.1.49136.1.3.11.0
Indicates system uptime in
hours
All
Measured in hours
Read-only
OID
Description
Type
Parameters
Access
.1.3.6.1.4.1.49136.1.4.1.0
Internal temperature
All
°C
Read- only
.1.3.6.1.4.1.49136.1.4.2.0
External temperature
.1.3.6.1.4.1.49136.1.4.3.0
Internal heat sink
temperature