DC UPS
4
CHARGER CONFIGURATION
Manually set the battery charger to the desired charging current
.
In the table below, you can see the output power according to the charger configuration.
5
BATTERY CONNECTION
Connect the battery or battery bank to the indicated front connector, be careful to connect with the
correct voltage and polarity.
Caution
To install the battery bank, leave the batteries disconnected and switch on only
after connect the cables to the DC UPS.
Attention
Use only stationary lead acid or VRLA batteries, and be aware of proper battery
bank voltage.
Maximum charger
Minimum charger
Model
Total output
power
Equipment
power
Equipment
output current
Charger
current
Equipment
power
Equipment current
Charger
current
12V 20A
240W
120W
10A
10A
228W
19A
1A
24V 10A
240W
120W
5A
5A
216W
9A
1A
24V 15A
360W
120W
5A
10A
336W
14A
1A
-48V 5A
270W
108W
2A
3A
216W
4A
1A
-48V 10A
540W
270W
5A
5A
486W
9A
1A
1A charger current mode
Key 1, 2, 3 and 4 down
3A charger current mode
Key 1 up
5A charger current mode
Key 1 and 2 up
10A charger current mode
Key 1, 2 and 3 up, except for 24V/10A
AC/DC UPS, because this setting is
equivalent to 5A load current mode.
Battery type VRLA (In VRLA mode there is no
equalization stage in the battery charge)
Key 4 up
12V and 24V DC UPS
-48V DC UPS
1A charger current mode
Key 1 up
3A charger current mode
Key 1 and 2 up
5A charger current mode
Key 1, 2, 3 up
Battery type VRLA (In VRLA mode there is no
equalization stage in the battery charge)
Key 4 up
Ground bus