DC UPS

 

www.algcom.com.br

 

 

 

 
 

The watchdog configuration screen allows the user to enter the IP addresses that will be monitored, 
the time between the monitoring tests and the respective output of the DC UPS that will act in the 
event of a negative response. Monitoring is done by sending a ping to the registered IP. The ping 
response timeout is fixed in 5 seconds. After the non-ping response timeout, the faulty IP output will be 
reset. The user defines the period between pings sends in minutes.

 

 

                  

Subgroup 1 – DC UPS Output Parameters 

 

 

 

 

Subgroup 2 – Charger Parameters 

 

 

 
 
 
 
 
 
 
 

 
 
 
 

 

OID

 

Description

 

Type 

Parameters 

Access

 

.1.3.6.1.4.1.49136.1.1.1.0 

Voltage measured at DC UPS output 

All 

V (Volts) 

Read-only 

.1.3.6.1.4.1.49136.1.1.2.0 

Current measured at DC UPS output 

A (Amp) 

OID

 

Description

 

Type 

Parameters 

Access

 

.1.3.6.1.4.1.49136.1.2.1.0 

Voltage measured in 

the battery 

All 

V (Volts) 

 

Read- only 

.1.3.6.1.4.1.49136.1.2.2.0 

Current measured in 

the battery 

A (Amp) 

.1.3.6.1.4.1.49136.1.2.3.0 

Battery charger 

status 

0x00=CHARGER_BATTERY_NOT_CONNECTED 

0x01=CHARGER_WRONG_VOLTAGE_BATTERY 

0x02=CHARGER_NOBREAK 

0x03=CHARGER_CURRENT_CONST 

0x04=CHARGER_EQUALIZATION 

0x05=CHARGER_FLUTUATION 

0x06=CHARGER_NOBREAK_TIMEOUT 

 

 

14 WATCHDOG CONFIGURATION SCREEN

 

 

15 DESCRIPTION OF THE SNMP INTERFACE 

 

 

Содержание FN-4800-10-SNMP

Страница 1: ...have justacquired an ALGcomproduct Thanks foryour trust at choosing our company We develop products to offer the best and most modern solutions in telecommunications 11510050074_V2 FN FN SNMP DC UPS...

Страница 2: ...y present can cause death or injury if the precautions in this manual are ignored Attention Please follow the instructions contained in this manual carefully If you have any doubt please contact quali...

Страница 3: ...the DC UPS is being powered by the AC input F CHARGING BATTERY INDICATOR LED Indicates that the DC UPS is charging the battery bank G DISCHARGING BATTERY INDICATOR LED Indicates that the DC UPS is dis...

Страница 4: ...s conductor or connect the ground through the AC input connector Attention The connection to protective ground is mandatory It can be connected through power cable or chassis connection N AC INPUT CON...

Страница 5: ...the protective ground connection to the ground bus For 48V DC UPS The outputs 0V of the DC UPS are isolated from the ground being optional the connection to the system and grounding For 48V DC UPS To...

Страница 6: ...nt power Equipment output current Charger current Equipment power Equipment current Charger current 12V 20A 240W 120W 10A 10A 228W 19A 1A 24V 10A 240W 120W 5A 5A 216W 9A 1A 24V 15A 360W 120W 5A 10A 33...

Страница 7: ...ng stage Connect the AC power to the DC UPS Connect the AC power in the back of the DC UPS DC UPS output current Recommended minimum gauge 0 10A 1mm ou 16AWG 10 16A 1 5mm ou 14AWG 16 25A 2 5mm ou 12AW...

Страница 8: ...CONNECTION Measure the output voltage to see if it is suitable for your equipment Attention Check the voltage of the equipment connected to the DC UPS output Use a voltmeter to measure the output volt...

Страница 9: ...work connect an Ethernet Cable 2 The factory setting is as follows IP 192 168 1 50 User name admin Password admin If you need to return to the initial IP configuration and password press the Reset but...

Страница 10: ...he last 10 minutes Indicates if there has been a drop in the AC supply voltage in the last 10 minutes from the time the information is being displayed making it possible to monitor grid instabilities...

Страница 11: ...ers Subgroup 2 Charger Parameters OID Description Type Parameters Access 1 3 6 1 4 1 49136 1 1 1 0 Voltage measured at DC UPS output All V Volts Read only 1 3 6 1 4 1 49136 1 1 2 0 Current measured at...

Страница 12: ...PS Occurs when the DC UPS is operating at a power above the specified All 0 normal 1 overheating Read only 1 3 6 1 4 1 49136 1 3 6 0 Indicates general overload at DC UPS Occurs when the DC UPS is oper...

Страница 13: ...tchdog 5 action for 10 minutes since the last event occurred All 0 normal 1 watchdog actuated in the last 10 minutes Read only 1 3 6 1 4 1 49136 1 7 5 0 Indicates the configured watchdog 6 action for...

Страница 14: ...ightning or various atmospheric discharges Overvoltage Protects against the effects of electrical distribution networkmaneuvers Falls Protects against the effect that happens in installations when the...

Страница 15: ...of the electronic device piece of equipment 3 Warranty Exclusions The warranty will not cover and it is the sole responsibility of the buyer any damages caused by violation modification change of com...

Страница 16: ...of the product have three 3 months warranty For products repaired within the warranty period the warranty expiration date remains the same 6 Warranty Service For products that were not purchased dire...

Отзывы: