DC UPS
The watchdog configuration screen allows the user to enter the IP addresses that will be monitored,
the time between the monitoring tests and the respective output of the DC UPS that will act in the
event of a negative response. Monitoring is done by sending a ping to the registered IP. The ping
response timeout is fixed in 5 seconds. After the non-ping response timeout, the faulty IP output will be
reset. The user defines the period between pings sends in minutes.
Subgroup 1 – DC UPS Output Parameters
Subgroup 2 – Charger Parameters
OID
Description
Type
Parameters
Access
.1.3.6.1.4.1.49136.1.1.1.0
Voltage measured at DC UPS output
All
V (Volts)
Read-only
.1.3.6.1.4.1.49136.1.1.2.0
Current measured at DC UPS output
A (Amp)
OID
Description
Type
Parameters
Access
.1.3.6.1.4.1.49136.1.2.1.0
Voltage measured in
the battery
All
V (Volts)
Read- only
.1.3.6.1.4.1.49136.1.2.2.0
Current measured in
the battery
A (Amp)
.1.3.6.1.4.1.49136.1.2.3.0
Battery charger
status
0x00=CHARGER_BATTERY_NOT_CONNECTED
0x01=CHARGER_WRONG_VOLTAGE_BATTERY
0x02=CHARGER_NOBREAK
0x03=CHARGER_CURRENT_CONST
0x04=CHARGER_EQUALIZATION
0x05=CHARGER_FLUTUATION
0x06=CHARGER_NOBREAK_TIMEOUT
14 WATCHDOG CONFIGURATION SCREEN
15 DESCRIPTION OF THE SNMP INTERFACE