13
17. This shall be accompanied by one of the following:
a. One side of the enclosure shall be completely open; or
b. For an enclosure having four sides, a top and a bottom (at least two) ventilation openings at
cylinder valve level shall be provided in the side wall, equally sized, spaced at 180 degrees
(3.14 rad), and unobstructed.
18. Each opening shall have a total free area of not less than ½ in
2
/lb. (7.1 cm
2
/kg) of stored fuel ca-
pacity and not less than a total free area of 10 in
2
(64.5 cm
2
).
Example: 20 Lb. cylinder = 10 in
2
19. The ventilation opening(s) shall be provided at floor level and shall have a total free area of not
less than ½ in
2
/lb. (7.1 cm
2
/kg) of stored fuel capacity and not less than a total free area of 10 in
2
(64.5 cm
2
).
20. If ventilation openings at floor level are in a side wall, there shall be at least two openings. The bot-
tom of the openings shall be at floor level and the upper edge no more than 5 in (127 mm) above
the floor. The openings shall be equally sized, spaced at 180 degrees (3.14 rad) and unobstructed.
21. Every opening shall have minimum dimensions so as to permit the entrance of a 1/8 in (3.2 mm)
diameter rod.
LP GAS CONNECTION TO LP PIPED SYSTEMS:
An LP piped system is one with a large central LP tank that feeds the entire household. Those systems
are normally equipped with a high pressure regulator by the large LP tank and low pressure regulators
close to the home.
The gas line connectors must comply with the
Standard for Connectors for Outdoor Gas Appliances
and Manufactured Homes, ANSI Z21.75 • CAS 6.27
, and suitable for outside installation. The maximum
length of the connection shal be 6 Ft. (1.82 m)
GAS CONNECTION - NATURAL GAS (NG)
NEVER CONNECT THE PIZZA OVEN TO AN UNREGULATED GAS SUPPLY.
Before proceeding, ensure the oven is fitted for natural gas.
Connecting to an improper gas type will result in poor perfor-
mance and increased risk of damage or injury.
Total gas consumption (per hour) with all burners set on “HI” is
a follows:
Hearth & Rear Burner
38,000 BTUH Total
The installation of this appliance must conform with local codes
or, in the absence of local codes, to the national fuel gas code,
ANSI Z223.1a-1988. Installation in Canada must be in accord-
ance with the Standard CAN/ CGA-B149.1 Natural Gas Installa-
tion or CAN/CGA-B149.2, Propane Installation Code.
Manifold pressure with NG:
Operating:
5.0” W.C. (.14 PSI)
Non-operating:
5.5” W.C. (.16 PSI)
Optimum pressure: 7.0” W.C. (.25 PSI)
NOTE:
To ensure proper heating performance of this appli-
ance, verify that the gas line supply pressure is adequate (7.0”
W.C. supply pressure is preferred) to maintain 5” W.C. manifold
pressure.
SHUT OFF HAND VALVE
MUST BE LOCATED IN
ACCESSIBLE AREA
INCOMING NG
GAS SUPPLY
1/2” Ø - NG
FLEXIBLE HOSE
Figure # 7