The Ø100-mm flue pipe from the pellet boiler to the chimney should have the following characteristics: 

 

Total length maximum 5 m (in the case of a larger connection, increase the diameter of the connecting pipe to Ø150 

mm),  

 

Each knee of 90˚ reduces the total length of the flue pipe by 1 m, which means that if you have one knee, the total 

length can be 4 m, two knees 3 m, etc. 

 

The cap needed for cleaning should be located on each knee;  

 

The connections between the pipes should be sealed. 

 

If there is excessive resistance in the smoke discharge system (numerous knees, inadequate endings, bottlenecks, 

etc.), the discharge of flue gases is not guaranteed and the connection pipes and knees should have larger dimensions – Ø150 
mm. Similarly, in case the chimney does not allow proper flue gas discharge, there may be an irregularity in operation and, 
consequently, the Como Compact 32 Boiler  alarm may be activated. It is recommended that the chimney is checked by a 
qualified person before installing the Commo Compact 32 Boiler . 

The system for discharging smoke from the pellet boiler operates thanks to the underpressure that occurs in the 

combustion chamber and barely noticeable pressure in the flue pipe Ø100 mm. Therefore, make sure that the flue pipe is 
completely sealed. 

It is necessary to carefully analyse the position and condition of the space through which the chimney passes. If the 

flue pipe passes through the wall and/or roof, it should be properly insulated in accordance with fire safety regulations. 

Make sure that there is sufficient combustion air in the room where the boiler is located. The air supply pipe should 

have at least a 110-mm diameter and it should not be longer than 10 m. For each knee of 90˚, the maximum length is reduced 
by 1 m. If the pipe is too long, it is necessary to increase the diameter of the air supply pipe. 

If a grid is placed on the facade, the air inlet opening should be at least 100 cm

2

 or bigger. The boiler operates at 220-

230 V – 50 Hz. Ensure that the electrical cables do not go under the boiler , that they are away from hot surfaces and that they 
cannot come in contact with any sharp objects that could damage them. If the boiler is electrically overloaded, this may 
significantly shorten the service life of the electrical components of the boiler . 

 

Never turn off the power supply by pulling out the plug while there is still flame in the boiler . This may damage the 

boiler seriously and jeopardize the proper operation of the boiler .    

 

 

AIR SUPPLY 

The combustion air must be supplied to the room with the boiler. The room must be continuously aired. 
The fresh air opening must be at the bottom of the room and must let in the air. 
A) Combustion air supply by pipeline through basements. This connection option preheats the combustion air, which is 

useful for good and clean combustion. Installation of pipelines in the basement is simple. 

B) Combustion air supply through basements. The combustion air is preheated. The basement space must be separated 

from the ventilation system of the house and open to the outside. Avoid high levels of dust and moisture. 

V) Combustion air supply from above. Air supply from above can only be performed with tested flue systems. 
In this case, you must calculate the dimensioning of the flue! 
D) Combustion air supply directly from outside. If the air is supplied directly through the outer wall, the combustion air is 

only slightly preheated, which is unfavorable for clean combustion. In this case, there is also a risk of condensation! 

NOTE: We do not recommend these versions of the air supply! However, if you use these options, consult a qualified 

professional. 

The room with the heating appliance must have a sufficient supply of fresh air. If the windows and doors are hermetically 

sealed or there are air extracting devices such as a hoods, hair dryers, fans, etc. located in the room with the boiler, 
combustion air (fresh air) must be supplied from outside. In any case, this should be discussed with the competent 
chimneysweeper before installing the boiler.  

 

Содержание COMMO COMPACT 32

Страница 1: ...COMPACT 32 Installation Operation and Maintenance Manual This product meets the requirements of the Ecodesign Directive in terms of efficiency and air pollution level in order to contribute to the re...

Страница 2: ...ACCUMULATING BOILER ETC 18 LITRE EXPANSION TANK ENOUGH FOR 37 5 KW HEATING POWER AUTOMATIC AIR VENT VALVE SET ON THE HOT WATER OUTLET FROM THE BOILER SAFETY VALVE INSTALLED ON THE HOT WATER OUTLET FRO...

Страница 3: ...IONAL MAINTENANCE 10 CHARACTERISTIC BUILT IN ELEMENTS 11 CIRCULATION PUMP 11 EXPANSION TANK 11 FILL AND DRAIN COCK 11 ELECTRONIC SYSTEM 11 NON RETURN VALVE AUTOMATIC AIR VENT VALVE SAFETY VALVE AND WA...

Страница 4: ...Pellet boiler hydraulic installation diagram radiator and floor heating 27 Pellet boiler hydraulic installation diagram accumulation tank 28...

Страница 5: ...approach the boiler while in operation with the intention of playing This appliance can be used by children aged 8 and older and persons with reduced physical sensory or mental abilities if they are...

Страница 6: ...this document The installer is to check whether the air supply pipes correspond to the type of the installed boiler The electrical connections must not be executed with the use of temporary and or uns...

Страница 7: ...east 100 cm2 or bigger The boiler operates at 220 230 V 50 Hz Ensure that the electrical cables do not go under the boiler that they are away from hot surfaces and that they cannot come in contact wit...

Страница 8: ...the qualified chimney sweep Flue gases can be discharged directly into the chimney only if it has a cap for the purposes of inspection and cleaning and if its cross section is up to 20 x 20 cm i e if...

Страница 9: ...for a longer distance In this case the length is up to 8m INSULATION AND DIAMETER OF THE OPENINGS ON THE ROOF Once the position of the boiler has been determined it is necessary to make a hole i e an...

Страница 10: ...Grounding is prescribed by the law Under no circumstances may the electrical cable be exposed to a temperature above 80 C The power cable is part of the equipment that is supplied with the boiler It i...

Страница 11: ...uality and do not use any other types of fuel Inform all users on possible risks and hazards and show them how to handle the pellet boiler If the boiler is placed on a wooden floor it should be insula...

Страница 12: ...ing value min 16 9 MJ kg or 4 7 kWh kg ash content below 0 7 DO NOT use the boiler for burning garbage Always take care of maximum safety GUIDELINES FOR SAFE IGNITING AND CLEANING THE BOILER NEVER use...

Страница 13: ...l forward and by lowering it Figure 12b Take the upper ashtray out and pour the ashes into the garbage bin Then clean the ashtray and the space around the ashtray in the boiler with the vacuum cleaner...

Страница 14: ...er clarifications The manufacturer does not have direct supervision over the work of the installer and cannot guarantee for the performed works or maintenance works In no case does the manufacturer as...

Страница 15: ...e careful when connecting to a heating installation so that it does not rotate When the pump does not operate for a long period of time there is a risk that the pump shaft jams and cannot start at the...

Страница 16: ...to the valve you must take the right side off when facing the boiler Valve safety cap should be loose not too tight so that the air could freely leave 7 4 5 3 SAFETY VALVE The safety valve is with R1...

Страница 17: ...firemen In order to preserve safety and proper functioning of the pellet boiler do not use chopped wood Do not use the boiler for burning garbage THE PELLET QUALITY IS VERY IMPORTANT The pellet quali...

Страница 18: ...system BOILER CONTROL SYSTEM The boiler has an advanced control system that allows safe efficient and reliable operation control and maximum functional utilization of the boiler It is characterized b...

Страница 19: ...outlet has been activated L4 Additional motor Led light is on Additional motor has been activated L5 Aux 2 outlet Led light is on Aux 2 outlet has been activated L6 Aux 3 outlet Led light is on Aux 3...

Страница 20: ...ode Link Error This message informs you that there is no communication between the LCD display and the controller in the boiler Standby Man This message appears if the system is in Standby Mode after...

Страница 21: ...eters Chrono Menu for selecting modality of the Chrono Program and boiler turn on off time Manual Load Menu for manual loading of the auger It is only feasible when the system is in the OFF state Time...

Страница 22: ...50 U04 1380 U05 1610 U06 1840 U07 2070 U11 1030 Note The calibration of the auger and flue gas motor should not be carried out without prior consultation with the authorized maintenance staff or repre...

Страница 23: ...hrono Program By entering the Chrono Menu you see two submenus Modality and Programming Press the P4 and P6 keys to choose one of the submenus and then enter it by pressing the P3 key When you enter t...

Страница 24: ...pressing the P4 and P6 keys the hours minutes years months and days are set By pressing the P3 key you enter the change mode and by pressing the P4 and P6 keys you change the value If you press the P...

Страница 25: ...lighter Ignition Preload At this stage pellets are preloaded i e the auger loads a certain quantity of pellets that is necessary for ignition At this stage the lighter auger and flue gas motor are act...

Страница 26: ...The minimum duration of this phase is 300 seconds and the flue gas temperature needs to be less than 70 C in order to extinguish the furnace completely OFF In this phase the boiler is extinguished flu...

Страница 27: ...he furnace to extinguish and then press the P2 key for more than 3 seconds Check the condition and quality of the used pellet The appropriate flue gas temperature has not been reached during the Ignit...

Страница 28: ...an also be entrusted to a third person who is licensed for such activities INDICATION In any case you must comply with the laws of the country in which the pellet boiler is installed WARNING All disas...

Страница 29: ...r mg m3 26 2 Flue gas mass at nominal power kg s 0 0175 Flue gas mass at reduced power kg s 0 0072 Maximum operating water pressure bar 2 Maximum operating water temperature C 80 Boiler capacity l 68...

Страница 30: ...COMMO CONTACT 32 BOILER HYDRAULIC INSTALLATIONS DIAGRAM OF COMMO CONTACT 32 PELLET BOILER In order to reduce the risk of condensation install a three way mixing valve with a pipe thermostat when insta...

Страница 31: ...ydraulic installation diagram radiator and floor heating Legenda 1 Pellet boiler 2 Three way mixing valve with pipe thermostat Legenda 1 Pellet boiler 2 Hydraulic separator 3 Circulation pump 4 Three...

Страница 32: ...aulic installation diagram accumulation tank Legend 1 Pellet boiler 2 Air vent 3 Safety valve 3 bar 4 Air vent 5 Circulation pump 6 Three way mixing valve with pipe thermostat 7 Accumulation tank BUFF...

Отзывы: