2
Whether the room in which the boiler is being installed is appropriate, i.e. minimum size of the room in which the
boiler is to be installed,
Compliance with the flue gas regulations set forth in the instructions supplied by the manufacturer of the heating
device
The internal chimney diameter, the material the chimney is made of, whether it is flat and has a regular shape,
whether there are any obstacles and barriers in the chimney,
The height and vertical extension of the chimney,
The existence and suitability of a wind resistant protective cap of the chimney,
The possibility of providing the external air intake,
The possibility of the simultaneous use of the heat source with other equipment already existing in that place.
If the above mentioned standards have been satisfied, then the installer may proceed with the installation of the boiler .
The instructions provided by the boiler manufacturer, as well as the fire prevention standards and safety standards must be
observed.
After the boiler has been turned on for the first time, the system must be put into a trial operation for at least 30 minutes in
order to check that all the required conditions have been met.
Once the installation has been carried out, the installer is obliged to provide the client with the following:
Installation, Operation and Maintenance Manual issued by the boiler manufacturer (if such a manual has not been
delivered with the boiler ),
The documents required by applicable regulations,
The installer must teach the client how to handle the device, how to perform regular maintenance and cleaning.
INSTALLATION
The buyer shall be fully responsible for the activities carried out at the installation site.
Prior to installing the boiler , the installer should check if all the safety requirements are met, particularly the following:
The installer is to ensure that the boiler installation is in accordance with local, national and European standards.
The installer is to adhere to all requirements stated in this document.
The installer is to check whether the air supply pipes correspond to the type of the installed boiler .
The electrical connections must not be executed with the use of temporary and/or unsuitable cables.
The installer is to check the grounding of the electrical installation.
The installer must always use personal protective equipment and observe all prescribed precautionary measures.
The installer must always leave enough space for maintenance work.
After completion of the installation, the installer is to measure the emission of flue gases.
PLACING THE BOILER
We advise you to unpack the boiler only when it is put in the place where it is to be installed.
If the surrounding walls or floor are made of materials that are not heat resistant, appropriate protection made of
incombustible insulation material should be used.
In order to protect the floor from inflammable materials, you should put a metal plate 3 to 4 mm thick on the floor
under the boiler that would protrude for 30 cm ahead of the boiler front.
The pellet boiler should be installed in accordance with the diagram which determines the distance from the walls (Figure 2).
Figure 2
All minimum safety distances are indicated on the product data plate, DO NOT use lower values than specified (see
INFORMATION ON CE MARKING).
. If the pellet boiler is installed in a boiler room where there are other air suction devices (other boiler s, various types of
suction fans, etc.), make sure that the volume of air entering the room is satisfactory to guarantee the safe operation of the
boiler .
If the chimney passes through the ceiling, it must be sufficiently insulated with a non-inflammable insulating
material.
Once the boiler is placed, it should be levelled (brought to a horizontal position) with its adjustable legs. It is desirable
that the back of the boiler is raised to be 5-6mm higher than the front part so that the air from the upper part of the boiler may
be discharged completely.
The smoke discharge system MUST NOT be connected to:
The flue pipe used by another heat generator (boiler s, furnaces, fireplaces, etc.),
The air exhaust system (hoods, suction fans, etc.).
It is forbidden to install flue gas flow control units!