APPENDIX A: FAI Input Wiring Applications

March 25, 2013

AlarmSaf 65A Industrial Way, Wilmington, MA 01887 978 658 6717 

www.alarmsaf.com

Page 2

Remote normally open, dry contact or open 
collector trip using the internal voltage source of 
the FAIM.
Internal FAI Mode jumper (J1) must be set to the 

right.

Remote normally closed, dry contact trip using the 
internal voltage source of the FAIM.
Internal FAI Mode jumper (J1) must be set to the 

right.

Remote normally open, dry contact or open 
collector trip using the internal voltage source of 
the FAIM with latch function. 

Remote reset switch is used to unlatch FAI 
condition after system alarm is restored to normal 
supervisory condition.

Internal FAI Mode jumper (J1) must be set to the 
right.

Содержание PS5-M

Страница 1: ...M Power Supply Battery Charger with Fire Alarm Input Module Installation Manual This Installation manual is made up of the following separate Installation Instructions for the Power Supply and Fire Al...

Страница 2: ...USS 1 J4 ABC COM FLT AC FLT COM FLT GND FLT AC FLT VOLTAGE SELECT 24V 12V BAT DETECT EARTH GND DETECT AC ON EARTH HOT NEUTRAL J1 BATTERY FUSE Model PS5 M Power Supply Battery Charger Operating and Ins...

Страница 3: ...n a manner which prevents unintentional operation from employees or other personnel working about the premises by falling objects by building vibration and by similar causes NOTICE This equipment is n...

Страница 4: ...3 8 Fusing 11 3 7 Fault Reporting Terminals 10 3 6 Battery Terminals 10 3 5 Output Terminals 9 3 4 ABC Connectors and Harnesses 8 3 3 AC Input Connection 7 3 2 Connector Descriptions and Electrical R...

Страница 5: ...her of two available power busses Buss 1 or Buss 2 All units can charge up to 80 AH of battery within 48 hours 40 AH in 24 hours while supplying full rated load Full fault detection including battery...

Страница 6: ...ts of the Local Authority Having Jurisdiction LAHJ FCC Compliance This equipment has been tested and found to comply with the limits for Class A digital device pursuant to Part 15 of FCC rules These l...

Страница 7: ...ax Output 80 mA Maximum Plus total output load including accessory boards Standby Load While on Battery 170W max Input Power All Models 120 VAC or 230 VAC nominal 50 60 Hz Input Voltage Product Use Wh...

Страница 8: ...Hz Must be configured for 230 VAC prior to use See Fig 3 3 1 5 Pin AC Line connector J1 Rating Description Terminal Connector Figure 3 2 1 JP3 DC DC BAT BAT JP5 JP6 JP7 BUSS 2 BUSS 1 J4 ABC COM FLT AC...

Страница 9: ...put or damage to the supply will occur See Figure 3 3 1 Note The AC input connector is a convenient means for AC disconnect since the connector is fully shrouded when disconnected Note The Green or Gr...

Страница 10: ...or Buss 2 3 4 2 Cable Types ABC 04 18 inches Brown 00522 8 8 ABC 03 8 inches Brown 00521 8 8 Description Length Color AS PN Cable Type ABC 03 Used to connect the PS5 M to an accessory board or to conn...

Страница 11: ...here are no batteries on the PS5 M it is normal for there to be no voltage on the battery terminals The charger does not enable until it senses a battery on the terminals Note Connecting batteries in...

Страница 12: ...FLT GND FLT AC FLT COMMON FAULT FIELD WIRING TERMINALS AC FAULT FIELD WIRING TERMINALS C NC NO C NC NO No Fault Fault Fault Internal Fault No Fault Fault Reversed Battery Connection No Fault Fault Bl...

Страница 13: ...available Automotive Miniature fuses Type ATM Both fuses are rated at 15A ATM 15 The AC Input fuse is a soldered in non replaceable fuse If it is determined that this fuse has opened the PS5 M board...

Страница 14: ...mately inch 3 Using the two upper keyholes mount the cabinet over the two screws 4 Mark the two lower holes remove the cabinet and drill the lower mounting holes 5 Mount the cabinet install the remain...

Страница 15: ...ing Locate the battery terminals These terminals are non removable and accept wire sizes between 12 and 22 AWG Polarity is notated on the PCB If the PS5 M is set for 12 VDC connect a single 12V batter...

Страница 16: ...NABLE AC PRESENCE VISUAL INDICATOR 12V 24V Figure 5 1 1 5 2 Jumper Settings For proper operation the jumpers on the PS5 M should be set appropriately These jumpers may be set with the unit powered or...

Страница 17: ...utput Green DC Output DC OK D15 Lights when AC voltage is present on the input Green AC Power AC ON D19 Conditions Color Description LED 5 3 1 AC ON D19 For safety reasons this LED illuminates any tim...

Страница 18: ...ble s Improper ABC cable connection Verify that output current is less than the rated current Excessive loading on output Verify fuse is intact Check wiring integrity before replacing fuse Blown batte...

Страница 19: ...harge 6 1 6 Maximum Battery Charger Capacity 80 Amphours 48 hour charge 6 1 7 Maximum Battery Charge Current 2A max at 12 or 24 VDC nominal 6 2 Temperature Specifications 6 2 1 Ambient Temperature Ran...

Страница 20: ...NPUT V V AlarmSaf c 2006 SAME TYPE AND RATING REPLACE FUSES ONLY WITH UTILISER UN FUSIBLE DE RECHANGE DE MEME FLT FAI B1 B1 B2 B2 RET PWR LTD DC1 DC2 DC1 DC2 DC1 DC2 B1 B2 FAI ATM 15 L BUSS 2 CONNECT...

Страница 21: ...or other personnel working about the premises by falling objects by building vibration and by similar causes NOTICE This equipment is not intended for use within the patient care areas of a Health Ca...

Страница 22: ...put Terminals 9 3 5 Input Terminals 9 4 Installation 10 11 4 1 Mounting 10 4 2 Wiring 11 4 3 Labeling 11 5 Operating the FAIM 12 14 5 1 Jumper Configuration 12 5 2 Visual Indicators 13 5 3 Troubleshoo...

Страница 23: ...on power limited output and one 1 6A PTC protected power limited output These outputs drop power upon the FAIM receiving a valid input signal Two methods of connection of the output to the ABC buss ar...

Страница 24: ...osed Circuit Television Equipment Canadian Standards ULC S527 Standard for Control Units for Fire Alarm Systems ULC S318 Standard for Power Supplies for Burglar Alarm Systems CAN CSA C22 2 No 107 1 01...

Страница 25: ...er supplies and jumper selections Outputs Power Input 12 24VDC Nominal 14 Amps maximum Control Input 9 33VDC 3 3mA Maximum Inputs Product Use When installed in accordance with all standards listed in...

Страница 26: ...ABC Input or Output P2 12 24V Nominal at 14A per Buss controlled by base supply s ABC Input or Output P1 Rating Description Terminal Connector Fig 3 2 1 TB2 P1 P2 D1 F1 D2 J1 J2 D12 D13 J3 D10 TB1 MOD...

Страница 27: ...ipment 3 3 4 Cable Types ABC 06 18 inches Red A099071 6 8 ABC 05 8 inches Red A099070 6 8 ABC 04 18 inches Brown A099069 8 8 ABC 03 8 inches Brown A099068 8 8 ABC 02 18 inches White A099063 6 6 ABC 01...

Страница 28: ...e FAIM s input terminals TB1 provide the control for the DC1 and DC2 outputs The input can be selected for fail safe or fail secure as well as for voltage input dry contact or open collector activatio...

Страница 29: ...doffs and secure using the included 6 32 x 3 8 screws 3 Connect ABC cable s appropriately See section 3 3 4 1 1 Mounting to an approved power supply 1 If not already present install the four 6 32 x 3...

Страница 30: ...he header Connect the wiring for the equipment to be powered to the terminal block The PC board is labeled with the output numbers and polarity See also Sections 3 2 and 3 4 Replace the terminal block...

Страница 31: ...required to reset the FAIM In addition to this jumper setting a specific wiring method is required to use the latching feature See Appendix A for details on wiring the FAIM s input terminals in the la...

Страница 32: ...available when lit DC2 D12 Indicates that the DC2 output has power available when lit TB2 P1 P2 D1 F1 D2 J1 J2 D12 D13 J3 D10 TB1 MODE FAI BUSS FAI FAIM 38 137 Rev B01 B A FAI INPUT V V AlarmSaf c 20...

Страница 33: ...put is activating properly Input not being activated Verify proper input and output jumper settings Improper Jumper Settings Input not operating as expected Verify correct state of input and input wir...

Страница 34: ...o 49 C 32 F to 120 F 6 2 2 Ambient Humidity 93 at 32 C 90 F Maximum 6 3 Mechanical Specifications 6 3 1 Weight 0 10 LBS Not including hardware or cables 6 3 2 Size 4 83 L x 2 10 W x 0 75 H Note Width...

Страница 35: ...arious wiring methods Verify all jumpers are set properly Remote normally open dry contact trip using the internal voltage source of the FAIM Internal FAI Mode jumper J1 must be set to the right Remot...

Страница 36: ...mper J1 must be set to the right Remote normally closed dry contact trip using the internal voltage source of the FAIM Internal FAI Mode jumper J1 must be set to the right Remote normally open dry con...

Отзывы: