Section 5
Operating the PS5-M
5.1 Output Voltage Selection
Before powering a system containing a PS5-M, the output voltage switch (SW1 - Voltage Select) must
be set for the proper output voltage or damage to the system could occur. Do not change the switch
setting while the unit is powered or damage to the system may occur. Set the switch towards the
green AC Visual Indicator for 12V, away from the green AC Visual Indicator for 24V (the PC board is
labeled with the voltage settings).
VO
L
T
A
G
E
SE
L
E
C
T
24V
12V
BA
T
DE
TECT
EA
R
T
H GND
DE
TECT
AC ON
OUTPUT VOLTAGE
SELECT SWITCH
EARTH GOUND
DETECTION ENABLE
BATTERY PRESENCE
DETECTION ENABLE
AC PRESENCE
VISUAL INDICATOR
12V
24V
Figure 5.1.1
5.2 Jumper Settings
For proper operation, the jumpers on the PS5-M should be set appropriately. These jumpers may be
set with the unit powered or un-powered.
Buss 1 (JP5 & JP7)
See section 5.2.3
ABC Buss Select
JP5, JP6, JP7 (Buss 1 / Buss
2)
Enable
Jumper On - Enable
Jumper Off - Disable
Earth Ground Fault
Detection
JP9 (Earth Ground Detect))
Enable
Jumper On - Enable
Jumper Off - Disable
Battery Presence Fault
Detection
JP10 (Bat Detect)
Default
Settings
Description
Jumper
5.2.1 JP10 (Bat Detect) - Battery Presence
This jumper allows disabling of the battery presence detection for applications where no backup
battery set is used.
PS5-M Installation Instructions
February 23, 2012
52-375 Rev A.03
Page 15 of 18