4.2 Wiring
4.2.1 Wire Routing
All wiring must be installed in accordance with NFPA70 [NEC760], NFPA72, and
all local code requirements.
Power Limited wiring requires that power limited and non-power limited wiring
remain physically separated. Any power limited circuit entering the enclosure
must remain at least one quarter inch (
¼
”) away from any non-power limited
circuit wiring. Any power limited circuit wiring must enter and exit the enclosure
through different knockouts than non-power limited circuit wiring.
Wiring within the enclosure should be routed around the perimeter of the
cabinet. It should not be routed across the circuit boards. See the enclosure’s
documentation for complete wire routing instructions.
4.2.2 ABC Connector
See section 3.3
4.2.3 Output Wiring
Locate the output wiring terminal block (TB2) on the PC board and remove the
terminal block from the header. Connect the wiring for the equipment to be
powered to the terminal block. The PC board is labeled with the output numbers
and polarity (See also Sections 3.2 and 3.4). Replace the terminal block on the
header.
NOTE: Wire size for these terminals must be 22-14 AWG.
4.2.4 Fire Alarm Input Wiring
Locate the input wiring terminal block (TB1) on the PC board and remove the
terminal block from the header. Connect the wiring for the fire alarm input to the
terminal block. The PC board is labeled with the terminal designations (See also
Sections 3.2, 3.5, and 5.1.4). Replace the terminal block on the header.
NOTE: Wire size for these terminals must be 22-14 AWG.
4.3 Labeling
If the FAIM was purchased separately from the power supply unit, the supplied
label must be applied to the inside cover of the power supply’s enclosure. The
label shall not cover any ventilation holes or other labeling on the enclosure.
FAIM Installation Instructions
2009/10/30 16:12:34
52-382 Rev A.01
Page 11 of 15
AlarmSaf
65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com