15
Model No: AC-F30HG
Version 1.0
Indoor unit installation
1. Install the indoor unit temporarily.
a. Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using a
nut and washer from the upper and lower sides of the hanger bracket. The washer
fixing plate will prevent the washer from falling.
b. Refer to the paper pad for installation for ceiling opening dimension.
c. The center of the ceiling is indicated on the paper pad for installation, the center of the
unit is indicated on the label attached to the unit and on the paper pad for installation.
d. Fix the paper pad to the unit with screws ( 3)
2. Refer to diagram 3, adjust the unit to the right position for installation.
3. Check if the unit is horizontally level.
a. The indoor unit is equipped with a built-in drainage pump and float switch at each of
the unit’s 4 corners, verify that it is level by using a water level or a water filled vinyl
tube. (If the unit is tilted against condensate flow the float switch my malfunction and
cause water to drip.)
4. Remove the washer fixing plate used for preventing the washer from falling and tighten the
upper nut.
5. Remove the paper pad for installation
Warning: Tighten the nut to prevent the unit from falling.
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание AC-F30HG
Страница 1: ...Air Conditional Service Manual http splitoff ru tehn doc html...
Страница 2: ...Model No AC F30HG Version 1 0 2 Model AC F30HG http splitoff ru tehn doc html...
Страница 11: ...11 Model No AC F30HG Version 1 0 OUTDOOR UNIT http splitoff ru tehn doc html...
Страница 28: ...28 Model No AC F30HG Version 1 0 CIRCUIT DIAGRAM http splitoff ru tehn doc html...