Connection of refrigerant pipe
•
Be sure to use both a spanner and torque wrench together as shown in the drawing, connecting or
disconnecting pipes to/from the unit.
•
Refer to table 1 to determine the proper tightening torque (over tightening may damage the flare
and cause leaks.)
•
When connecting the flare nut, coat the flare both inside and outside with refrigerating machine oil
and initially tighten by hand 3 or 4 turns.
•
Check the pipe connector for gas leaks, then insulate it as shown in the drawing below.
•
Use sealing pad (11) to wrap joint between gas pipe and the insulation (8).
Table 1
Pipe gauge Tightening torque
Notes
9.52
30 ~ 40N.m
16
60 ~ 65N.m
12
45 ~ 50N.m
19
70 ~ 75N.m
KF(R)-50TW/E1
KF(R)-70TW/B
KF(R)-70TW/B1
KF(R)-120TW/B
Add 30g
Add 30g
Add 30g
Add 30g
The maximum length for refrigerant piping is 25 meters, when the length exceeds 10 meters, you should
charge additional (refrigerant as shown in following for per-meter added).