The working condition of the outdoor unit:
T
out
≥
16
o
C, the outdoor unit fan motor runs in low speed;
T
out
≤
13
o
C, the outdoor unit fan motor runs in high speed;
13
o
C < T
out
< 16
o
C, the outdoor unit fan motor runs in the old speed; the outdoor unit fan motor
stop when it is defrosting.
The conditions of avoiding cold wind:
The indoor unit adjust the guider into horizontal first, indoor unit motor runs in high speed for
8 sec, then runs in low speed.
a. Compressor runs as soon as Tin achieve the temperature of starting unit, indoor unit
runs at low speed, guider is still horizontal, 30sec later, indoor unit fan motor runs in
the set speed, guider run in the set mode (it run in the max angle if it has not be set);
b. If T
in
does not achieve the temperature of starting unit, indoor unit fan motor runs in
the low speed and guider is horizontal.
The conditions of flowing the rest heat:
Once the compressor is stop, guider turn into horizontal, the indoor unit fan motor runs in low
speed.
The conditions of beginning defrosting:
After the unit continue heating for 44min, and detect T
con
≤
-8
o
C for 1min, the defrosting mode
act, guider turn into horizontal, the reversing valve, the indoor and outdoor unit fan motor stop.
If there is electrical heater in the unit, then it will be stopped first after 1min, reversing valve,
the indoor and outdoor unit fan motor stop.
The conditions of stopping defrosting:
After the unit continue defrosts for 10min or T
con
+10
o
C, the defrosting stop, the reversal valve
run, the outdoor fan motor runs, and the indoor unit fan motor will run in the condition of
avoiding the cold wind.
The working conditions of electrical heater:
When the indoor unit fan motor runs in high or middle speed and compressor runs, and T
eva
≤
44
o
C and T
in
23
o
C, or T
in
< T
set
–1
o
C, the electrical heater act.
When the indoor unit is stop or runs in low speed or compressor in stop, or T
eva
52
o
C, or T
in
≥
26
o
C, or T
in
T
set
+2
o
C, the electrical heater stop and will restart after 2min.
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание AC-F30HG
Страница 1: ...Air Conditional Service Manual http splitoff ru tehn doc html...
Страница 2: ...Model No AC F30HG Version 1 0 2 Model AC F30HG http splitoff ru tehn doc html...
Страница 11: ...11 Model No AC F30HG Version 1 0 OUTDOOR UNIT http splitoff ru tehn doc html...
Страница 28: ...28 Model No AC F30HG Version 1 0 CIRCUIT DIAGRAM http splitoff ru tehn doc html...