30
Model No: AC-F30HG
Version 1.0
4. The different controlling mode for the different function mode:
Under all of the modes, the compressor will continue work for 6min once it starts (except for the
protection of full-water), and be restart in 4min after it stops. At the beginning, the indoor unit fan motor
runs for 8sec in high speed, then change to the set fan speed; and it is same in the outdoor unit.
a. Cooling mode:
If Tin T
in
≥
T
set
+1
o
C , cooling mode act, compressor and outdoor unit run, and indoor unit run in
the set speed;
If T
in
≤
T
set
–1
o
C , the unit will be stop from cooling mode, compressor and outdoor unit stop,
and indoor unit still run in the set speed;
If T
set
-1
o
C < T
in
< T
set
+ 1
o
C , keep running in the old mode; In the cooling mode, the range of
T
set
is 16
o
C ~30
o
C .
Outdoor fan motor working state:
T
out
≥
27
o
C, outdoor fan motor runs in high speed;
T
out
≤
24
o
C, outdoor fan motor runs in low speed;
24
o
C < T
out
< 27
o
C, outdoor fan motor runs in old mode.
b. Drying mode:
If T
in
> T
set
+ 2
o
C, drying mode act, compressor, indoor unit fan motor run, the indoor unit fan
motor runs in low speed;
If T
set
–2
o
C
≤
T
in
≤
T
set
+ 2
o
C, compressor, indoor unit and outdoor run for 6 min, then stop for 3
min, then run by this cycle, the indoor unit fan motor runs in low speed;
If Tin<Tset-2 , compressor, outdoor unit fan motor, indoor unit fan motor stop.
In drying mode, the range of T
set
is 16
o
C ~30
o
C.
Outdoor fan motor working state:
T
out
≥
27
o
C, outdoor fan motor runs in high speed;
T
out
≤
24
o
C , outdoor fan motor runs in low speed;
24
o
C < T
out
< 27
o
C, outdoor fan motor runs in old speed.
c. Heating mode:
If T
in
≤
T
set
+ 1
o
C, heating mode act, reversing valve, compressor and outdoor unit fan motor
run, indoor unit fan motor runs in the set speed and the condition of avoiding the cold wind;
If T
in
≥
T
set
+ 3
o
C, compressor and outdoor unit fan motor stop, reversing valve is still electric,
the indoor unit fan motor runs in the condition of flowing the rest heat;
If T
set
+ 1
o
C < T
in
< T
set
+3
o
C, keep running the old mode;
In the heating mode, the range of T
set
is 16
o
C ~30
o
C.
In the heating mode, the valve will be electroless in 2 min after the unit is turned off.
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание AC-F30HG
Страница 1: ...Air Conditional Service Manual http splitoff ru tehn doc html...
Страница 2: ...Model No AC F30HG Version 1 0 2 Model AC F30HG http splitoff ru tehn doc html...
Страница 11: ...11 Model No AC F30HG Version 1 0 OUTDOOR UNIT http splitoff ru tehn doc html...
Страница 28: ...28 Model No AC F30HG Version 1 0 CIRCUIT DIAGRAM http splitoff ru tehn doc html...