19
Model No: AC-F30HG
Version 1.0
Electric wiring
•
All field supplied parts and materials must conform to local laws and regulations.
•
For electric wiring, refer to WIRING DIAGRAM ”attached to the unit body.
•
A skilled technician must perform all wiring.
•
A circuit breaker capable of shutting down power supply to the entire system and with at least 3
mm contact separation must be installed.
•
Earth properly.
•
Wiring must conform to national laws and regulations.
•
Installing the protector with not more than 30mA leakage current is a must.
•
If the supply cord is damaged, it must be replaced by the manufactory or its service agents or a
similarity qualified person in order to avoid a hazard.
Wiring of unit and the controller
•
Wiring of the indoor unit.
•
Remove the control box lid (1), pull the wires inside through rubber bush and wiring according to
the “ WIRING DIAGRAM ”, then tighten it with clamp.
•
Wiring of the controller.
•
Remove the control box lid (2), pull wires inside through rubber bush and connect to the controller.
•
Wrap the wire with sealing pad (12).
•
After wiring, tighten it with clamp and fix the control box lid (1),(2).
•
Heating and cooling connect the rubber wire (5-cords) to the power supply terminal board in
properly.
•
Cooling connect the rubber wire (3-cords) to the power supply terminal board properly.
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Содержание AC-F30HG
Страница 1: ...Air Conditional Service Manual http splitoff ru tehn doc html...
Страница 2: ...Model No AC F30HG Version 1 0 2 Model AC F30HG http splitoff ru tehn doc html...
Страница 11: ...11 Model No AC F30HG Version 1 0 OUTDOOR UNIT http splitoff ru tehn doc html...
Страница 28: ...28 Model No AC F30HG Version 1 0 CIRCUIT DIAGRAM http splitoff ru tehn doc html...