73
Rev 2.1
•
Select
Sensor only
for DHW demand from selected DHW modulation sensor
•
Select
DHW (S6) Switch
for DHW demand from DHW switch (switch replaces the DHW sensor) When sensor
input is shorted burner demand exist outlet sensor will provide the temperature control
•
Select
STAT Terminal
for DHW demand from STAT input
•
Select
Auto DHW (S6) or sensor only
for DHW demand from DHW switch and DHW sensor
5-3.3 To Change DHW Loop Priority Versus CH Loop
Configure
→
DHW – Domestic Hot Water Configuration
→
DHW Priority vs CH
Textbox
(Default: DHW > CH)
•
Select
CH > DHW
for no priority over CH loop
•
Select
DHW > CH
for priority over CH loop
This parameters determines the priority of DHW vs. the CH call-for heat, when both of these are enabled and active.
(If DHW has a lower priority, it may be boosted to the highest priority temporarily via the DHW Priority Time
parameter.)
5-3.4 To Change DHW Loop Priority Time
Configure
→
DHW – Domestic Hot Water Configuration
→
DHW Override Priority Time
Textbox (Default: 5m 0s)
•
Type in desired time. No limits on this parameter.
If this parameter is non-zero then a DHW demand will take priority over other demand sources for the specified time.
If this persists for longer than this time the priority will expire. The timer is reset when demand from the DHW source
turns off.
5-3.5 To Change DHW Loop Setpoint
Configure
→
DHW – Domestic Hot Water Configuration
→
Setpoint
Textbox (Default: 120
⁰
F)
•
Type in desired temperature between 32
⁰
F and 240
⁰
F (0
⁰
C and 115
⁰
C)
This Setpoint is used whenever the time-of-day switch is off or not connected (unused).
5-3.6 To Change DHW Loop Time Of Day Setpoint
Configure
→
DHW – Domestic Hot Water Configuration
→
Time of Day Setpoint
Textbox
(Default: 100
⁰
F)
•
Type in desired temperature between 32
⁰
F and 240
⁰
F (0
⁰
C and 115
⁰
C)
This Setpoint is used when the time-of-day switch is on.
5-3.7 To Change DHW Loop Off Hysteresis
Configure
→
DHW – Domestic Hot Water Configuration
→
On Hysteresis
Textbox (Default: 7
⁰
F)
•
Type in desired temperature between 2
⁰
F and 30
⁰
F (1
⁰
C and 16
⁰
C)
The on hysteresis is subtracted from the DHW Setpoint to determine the temperature at which DHW demand turns
on.
5-3.8 To Change DHW Loop On Hysteresis
Configure
→
DHW – Domestic Hot Water Configuration
→
Off Hysteresis
Textbox (Default: 7
⁰
F)
•
Type in desired temperature between 2
⁰
F and 30
⁰
F (1
⁰
C and 16
⁰
C)
The off hysteresis is added to the DHW Setpoint to determine the temperature at which DHW demand turns off.
5-3.9 To Change The DHW Hysteresis Step Time
Configure
→
DHW – Domestic Hot Water Configuration
→
Hysteresis Step Time
Textbox
(Default: 0m0s)
•
Type in desired time between 0 to 5 minutes
The time needed for one step of hysteresis shift, when the off hysteresis threshold or on hysteresis threshold is shifted
due to a burner-on or burner-off event, respectively. Zero disables this function.
Содержание A050-A300
Страница 21: ...21 Rev 2 1 Figure 2 4 Suggested Single Fuel Atlas Gas Piping Figure 2 5 Suggested Dual Fuel Atlas Gas Piping ...
Страница 28: ...28 Rev 2 1 ...
Страница 31: ...31 Rev 2 1 Figure 2 10 One Atlas One Tank Suggest Piping Diagram ...
Страница 32: ...32 Rev 2 1 Figure 2 11 One Atlas Two Tank Piping Diagram ...
Страница 33: ...33 Rev 2 1 Figure 2 12 Two Atlas One Tank Piping Diagram ...
Страница 34: ...34 Rev 2 1 Figure 2 13 Two Atlas Two Tank Piping Diagram ...
Страница 36: ...36 Rev 2 1 Figure 2 15 Two Atlas in Primary Secondary Loop Piping Diagram ...
Страница 113: ...113 Rev 2 1 ...