Firing rate
RPM
Fan speed
RPM
Flame signal
V
Header temperature
If enabled
Outlet temperature
Degrees
Inlet temperature
If enabled
DHW temperature
If enabled
Stack temperature
If enabled
Outdoor temperature
If enabled
Table 4.33 – Analog I/O Data
Analog I/O data is displayed as bar charts depicting the I/O level. Analog I/O that is not enabled for the installation
displays a blank I/O level. To see all analog I/O, use the horizontal scroll bar to move the view left and right.
4-37 Installer Checkouts – Diagnostics Tests
Pressing the
Diagnostics Test
button launches the diagnostic tests. The first test displayed on the right side of the
screen is the last selected test shown.
This screen enables the user to perform the following tests:
•
Modulation
Test:
Enables the user to verify that the burner is firing at the correct rate.
•
Pilot
Test:
Enables the user to verify that the pilot valve is functioning properly. The user can also perform burner
adjustments for the pilot flame.
•
Pump
Test:
Enables the user to verify that the correct pump is on or off. The Start Test button will test all pumps;
pressing an individual pump tests that pump only.
•
Burner
Switch:
This button turns the burner on or off.
Start Test:
Runs the test for 5 minutes.
4-38 System Time
System time can be configured in the Operator Interface and applied to all Honeywell Sola Controllers that exist in the
installation. A date and time is entered by the user at the Operator Interface and any data that is time stamped is marked
with the current time and date in the Operator Interface. The Operator Interface system clock is set by going to Setup on
the Home Screen and then selecting the
System Time
button on the Advanced Setup page. A screen similar to the
following
Figure 4.76
displays.
NOTE
: It’s important that the system time be set in the Operator Interface so correct time stamps are given to the
Honeywell Sola Controller lockouts. The Operator Interface time and date need to be set each time the Operator Interface
reboots.
Figure 4.76 –Operator Interface Date and Time
Содержание A050-A300
Страница 21: ...21 Rev 2 1 Figure 2 4 Suggested Single Fuel Atlas Gas Piping Figure 2 5 Suggested Dual Fuel Atlas Gas Piping ...
Страница 28: ...28 Rev 2 1 ...
Страница 31: ...31 Rev 2 1 Figure 2 10 One Atlas One Tank Suggest Piping Diagram ...
Страница 32: ...32 Rev 2 1 Figure 2 11 One Atlas Two Tank Piping Diagram ...
Страница 33: ...33 Rev 2 1 Figure 2 12 Two Atlas One Tank Piping Diagram ...
Страница 34: ...34 Rev 2 1 Figure 2 13 Two Atlas Two Tank Piping Diagram ...
Страница 36: ...36 Rev 2 1 Figure 2 15 Two Atlas in Primary Secondary Loop Piping Diagram ...
Страница 113: ...113 Rev 2 1 ...