78
Rev 2.1
5-8 Delta-T Limit Related Configuration
5-8.1 To Enable Or Disable Delta-T Limit
Configure
→
Delta T
→
Inlet to Outlet Flow
→
Delta-T Enable
Textbox (Default: No Delta-T)
•
Select
Enable
to enable Delta-T limit
•
Select
Disable
to disable Delta-T limit
This parameter enables or disables the entire delta-T limit function.
5-8.2 To Change Delta-T Limit Delay
Configure
→
Delta T
→
Inlet to Outlet Flow
→
Delta-T Delay
Textbox (Default: 5m0s)
•
Type in desired time between 0 to 5 minutes
This parameter provides the delay time for the Delta-T limit.
5-8.3 To Change Delta-T Limit Response
Configure
→
Delta T
→
Inlet to Outlet Flow
→
Delta-T Limit Response
Textbox (Default: Lockout)
•
Select
Lockout
to lockout in event of Delta-T limit
•
Select
Recycle & delay
to recycle and delay in event of Delta-T limit
•
Select
Recycle & delay
with retry limit
to recycle and delay in event of Delta-T limit up to Delta-T retry limit
If the temperature difference exceeds the limit and Recycle and delay is selected then the burner control recycles and
holds while waiting for a delay (see the Delta-T Limit Delay parameter) to expire.
5-8.4 To Change Delta-T Limit Degrees
Configure
→
Delta T
→
Inlet to Outlet Flow
→
Delta-T Degrees
Textbox (Default: A050-A075: 47, A100: 63, A150: 94,
A200: 63, A250: 79, A300: 94)
•
Type in desired temperature
If the outlet is hotter than the inlet temperature by the amount given by this parameter, the response defined for the
Delta-T Limit Response will occur. Stepped Modulation Limiting will occur as the temperature approaches this limit.
5-8.5 To Change Delta-T Retry Limit
Configure
→
Delta T
→
Inlet to Outlet Flow
→
Delta-T Retry Limit
Textbox (Default: 10)
•
Type in desired retry limit
How many of retry will be tolerated. If demand I not satisfied and this number of recycles had happened, then lockout
occurs.
5-8.6 To Enable Delta-T Rate Limit
Configure
→
Delta T
→
Inlet to Outlet Flow
→
Delta-T Rate Limit Enable
Textbox (Default: Disabled)
•
Select
Enable
to enable Delta-T rate limit
•
Select
Disable
to disable Delta-T rate limit
Enabling this parameter causes Stepped modulation to occur as Delta-T temperature limit approached.
5-8.7 To Change Delta-T Inverse Limit Time
Configure
→
Delta T
→
Inlet to Outlet Flow
→
Delta-T Inverse Limit Time
Textbox (Default: 30m0s)
•
Type in desired time
When temperature inversion detection is enabled for a pair of sensors, this parameter specifies a time during with this will
be tolerated.
5-8.8 To Change Delta-T Inverse Limit Response
Configure
→
Delta T
→
Inlet to Outlet Flow
→
Delta-T Inverse Limit Response
Textbox
(Default: Recycle & delay)
•
Select
Lockout
to lockout in event of Delta-T inverse limit
•
Select
Recycle & delay
to recycle and delay in event of Delta-T inverse limit
Содержание A050-A300
Страница 21: ...21 Rev 2 1 Figure 2 4 Suggested Single Fuel Atlas Gas Piping Figure 2 5 Suggested Dual Fuel Atlas Gas Piping ...
Страница 28: ...28 Rev 2 1 ...
Страница 31: ...31 Rev 2 1 Figure 2 10 One Atlas One Tank Suggest Piping Diagram ...
Страница 32: ...32 Rev 2 1 Figure 2 11 One Atlas Two Tank Piping Diagram ...
Страница 33: ...33 Rev 2 1 Figure 2 12 Two Atlas One Tank Piping Diagram ...
Страница 34: ...34 Rev 2 1 Figure 2 13 Two Atlas Two Tank Piping Diagram ...
Страница 36: ...36 Rev 2 1 Figure 2 15 Two Atlas in Primary Secondary Loop Piping Diagram ...
Страница 113: ...113 Rev 2 1 ...