(4) Installation of air return duct
The unit is with air return and is set as back return type when out of factory. When installation, it can be
changed to down return type.
Ceiling Concealed type indoor unit must be with air return duct when installation, as figure 3 and 4:
Ceiling
Air supply
Air return
A
Building roof
Air return box
0.5m or 5m
Air supply duct
Unit
Fig. 3
no obstacles
within 1m
Air outlet
grille
Fig. 4(for A)
Air supply
Unit
Air return
Air return box
Every air sending duct and air return duct shall be fixed on the ceiling prefabricated panel by the iron
bracket. The duct joint is sealed with the glue. The recommended distance between the edge of the air
return duct and the wall is over 150mm.
The distance from the air outlet of the duct to the air outlet of the air conditioner is decided by the
length of duct and static pressure terminal:
Installation of short and long ducts is as below figure, when connecting the short ducts, use the low
static pressure terminals, which is white, the distance from the air outlet of the duct to the air outlet of
the air conditioner shall be no more than 0.5 m; When connecting the long ducts, use the middle static
pressure terminals, which is red. The distance from the air outlet of the duct to the air outlet of the air
conditioner shall be no more than 5m.
Fan speed selection (when using high efficient filter)
The fan motor composes red terminal and white terminal, which has been set at standard position when
out of factory. When the static pressure is increased for using high efficient filter, you can change the
connector position on the side of electric control box.
Standard Style(set in Factory)
Yellow
Black
Blue
Red
Yellow
Orange
Black
Blue
Control Box
Fan motor terminal
Control Box
Yellow
Black
Red
Blue
Yellow
Black
Red
Blue
High Speed Style
Static pressure range Unit: Pa
Standard static pressure
Max. static pressure
0
20
Fan motor terminal
73
Содержание YCV280
Страница 1: ...Design Installation and Maintenance instruction R410A Heat Pump 50 Hz FlowLogic II 2016...
Страница 5: ...2 External appearance YCV280 Outdoor YCV335 YCV400 YCV450 5...
Страница 13: ...This range it 13...
Страница 18: ...18...
Страница 34: ...4 Piping diagram liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 34...
Страница 61: ...40 100 270 12 5 J 130 940 220 Evaporators of 16 is 2 row type evaporator of 18 24 are 3 row type DAV016 24 61...
Страница 62: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 62...
Страница 83: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 83...
Страница 134: ...6 5 55 7 9 5 95 795 5 8 669 755 6 5 9 995 95 855 5 7 9 9 9 6 5 755 5 779 9 9 9 9 755 85 685 FAV038 48 134...
Страница 135: ...AQXQVO LQIOZIU fckoc jcj_ a m jcj_ FFV cfn_l cfn_l h ch iil b_ n _r b ha_l 135...
Страница 170: ...C 938 1046 186 5 234 2 6 5 2 9 9 A B MODEL 3 Dimensions HAV007 16 HAV018 24 170...
Страница 171: ...4 Piping diagrams liquid pipe gas pipe EEV filter filter fan indoor heat exchanger 171...
Страница 178: ...Installation 8 178...
Страница 179: ...179...
Страница 180: ...HAV018 24 HAV007 16 180...
Страница 181: ...181...
Страница 185: ...9QTMUZQVUZ 86 97 6 96 8 786 8MU MY VN OYI Q 185...
Страница 186: ...0 CQWQUO LQIOYITZ hemqe lela c o lela GGX behpan behpan b j ej kkn da p at_d jcan 186...
Страница 200: ...N PR 6 MkjZeeh Sd_ji 62A B yt F vwv 200...
Страница 206: ...206...
Страница 208: ...208...
Страница 209: ...209...
Страница 210: ...210...
Страница 211: ...211...
Страница 212: ...212...
Страница 249: ...E Capacity compensation value at different piping length and drop 255...
Страница 260: ...outdoor1 outdoor2 outdoor3 outdoor1 outdoor2 outdoor3 Installation at high difference outdoor1 outdoor2 outdoor3 266...
Страница 280: ...286...
Страница 298: ...RWV02 FlowLogic 304...
Страница 309: ...Installation and connections Dimensions Connecting board 315...
Страница 315: ...Ports Each port have serial number like 1 2 3 8 System Brief 321...
Страница 322: ...Next Next Next 328...
Страница 324: ...Select mysql then click ok Then click close ODBC setting Open ODBC database in the route control panel manage tool 330...
Страница 325: ...Select system DNS Click and add 331...
Страница 326: ...Select mysql then click finish Input according to the below information in the page Password is 1 Click OK 332...
Страница 327: ...3 Software installation Next 333...
Страница 331: ...337...