You must check water tightness and the cleanliness of the installation before connecting the
Aqu@ Scop HT Split
.
For the
Aqu@ Scop HT Split
's WATER INLET and OUTLET connections, you must install manual stop cocks
with the same diameter as the main pipe work. This will enable maintenance work to be carried out on the
Aqu@ Scop HT Split
without having to bleed the entire system.
A link valve with pressure tap kit is available.
The
Aqu@ Scop HT Split
must be protected by a water filter. When connecting this device to the
Aqu@ Scop HT Split
, take care to keep the water filter sieve pointing downwards. A sludge trap should be fitted in the event of high
sludge build-ups.
WARNING!
Take care not to damage the hydraulic pipe links by applying too
much tightening pressure. Use a second wrench to compensate for
the tightening torque.
You should always use a counter-wrench for tightening valves.
To guarantee proper energy efficiency and compliance with current standards, water pipes passing through
uninhabited zones should be properly lagged to retain heat.
To achieve correct insulation with conductivity of 0.04 W/mK, lag the pipes with insulating material with a radial
thickness between 25mm and 30 mm.
THE MANUFACTURER'S WARRANTY IS VOID IF THE FILTER SUPPLIED WITH THE
Aqu@ Scop HT Split IS NOT INSTALLED TO PROTECT THE APPLIANCE
AN EXPANSION TANK ADAPTED TO THE VOLUME OF WATER IN THE INSTALLATION
MUST BE INSTALLED.
It is important to ensure that the mains water supply pressure is sufficient to fill the installation.
12.3. WATER TREATMENT WARNING
Using untreated or inadequately treated water in this appliance can lead to a build-up of limescale,
algae or sludge deposits and cause corrosion and erosion. As the manufacturer is not aware of
the components used in the hydraulic network, or of the quality of water used, the installer or the
owner should contact a specialised water treatment company. This issue is particularly important
and every care should be taken to ensure that circuit water is properly treated in order to avoid
problems associated with incorrect water distribution. A clogged water network will systematically
lead to premature wear of the appliance's components.
12.4. CONNECTION TO THE CENTRAL HEATING LOOP
12.5. HEAT INSULATION