41
Screen L3
Screen L4
Screen L1
Screen L2
RADIATOR HEAT CURVE PARAMETERS
20
25
30
35
40
45
50
55
60
65
70
-15
-10
-5
0
5
10
15
20
Outdoor temperature (°C)
Leaving water temperature setpoint (°C)
Correction Coef. 0,5
Correction Coef. 0,8
Correction Coef. 1,0
Base outd. T.
Base water SPT
Information screen for the outdoor temperature calculated automatically by the
Aqu@ Scop HT Split
. With the preceding default parameters, the value of 5.4°
C means that below an outdoor temperature of 5.4° C the
Aqu@ Scop HT Split
will start the large compressor or the two-stage compressor. Above 5.4° C the
Aqu@ Scop HT Split
will start the small compressor.
The value of the outdoor balance temperature displayed on
L4
is the one updated
by the
Aqu@ Scop HT Split
after running for some time, in the event that the
Aqu@ Scop HT Split
detects a lack of capacity with the small compressor.
Zero reset
: This is required in the event of changes to the heat curve parameters
in order for the
Aqu@ Scop HT Split
to register these changes. The parameter on
screen
L3
is then recopied into screen
L4
.
Altitude
: Installation site altitude, in km (e.g. 0.5km equals 500m. Default setting:
0).
Base outd. T.
: Typical outdoor temperature for the installation region (Default
setting: -7°C).
Corr. Coef.
: Correction Coefficient for the base of the slope. This is a simple way
of changing the water set temperature (Default setting: 0.8).
21.2.3. HEAT CURVE PARAMETERS
On the main menu (key
), use the
/
arrows to highlight the "
HEAT CURVE
" menu. Validate this
selection with the
key. This moves the display to the
L1
screen. Use the
and
/
keys to set the
following parameters:
Losses at base Outdoor Temp
: Estimated heat loss for the dwelling for an
ambient temperature of 20°C and a base outdoor temperature (e.g. -7°C). This
parameter is used to calculate the outdoor temperature that triggers the change
from small compressor mode to two-stage compressor mode. This value is capped
at the maximum capacity of the
Aqu@ Scop HT Split
model in question for this
same outdoor temperature (Default value = Maximum value).
Water outlet temperature at -07°C Outdoor temperature
: Outlet water
temperature required at the base outdoor temperature (-7°C for example) to have an ambient temperature of 20°C
(Default setting: 65°C).