Trouble shooting 4
INDOOR UNIT
INDOOR UNIT
Error Method:
Error Method:
POWER SUPPLY FREQUENCY
ABNORMAL
Detective Actuators:
Detective Actuators:
Circuitry in indoor unit Control PCB
Detective details:
Detective details:
When power is turned on, frequency defective occurred (test 2times
matching read Test is failed for 5 times in a row
)
Lower than 45Hz or higher than 66Hz.
30A
Circuit breaker
H07RN-F or
Equivalent
Min.5.0mm
Total length is
less than 50m
Connection cord
H07RN-F or
Equivalent
Max. 8.0mm
Min.5.0mm
Power supply
cord
Wire type
Size
Use
Check Point 1
Check Point 1
-
-
1 : Check the installation work
1 : Check the installation work
Follow the installation Manual if any installation failure is found.
Forecast of Cause
Forecast of Cause:
1.Relation of installation construction 2.Relation of unit
1) Use of standard material
1) Check connection of POWER CORD
2) Power supply circuit (voltage drop / Noise etc.)
2) Check Control PCB (Parts defective)
1)Check the voltage of supply voltage AC220V between (L) - (N).
If AC does not appear, check the circuitry of power supply side.
2)Check the wiring (incorrect wiring / loose wiring) of connection cable.
If there was an incorrect wiring or loose wiring, turn off the breaker and then repair.
Check Point 2
Check Point 2
-
-
1 : Check connection of POWER CORD
1 : Check connection of POWER CORD
Check Cable / Breaker
Check if any loose connection or removal of cable.
Check Point 2
Check Point 2
-
-
2 : Check Electrical Component of Indoor Unit
2 : Check Electrical Component of Indoor Unit
Check connection / removal / incorrect wiring of all the connectors.
Check if short mark or corrosion is on PCB
Replace Control PCB and set up the original address,then check the
normal operation.
Check Point 1
Check Point 1
-
-
2 : Check Power supply
2 : Check Power supply
Check external cause (Power supply)
Instant Drop
Check if there is an electric equipment with a large load in the same circuit.
Instant Power Outage
Check if there is a defective contact or leakage in the power supply.
Noise
Check if there is any equipment that cause the harmonic wave near the power line.
(Neon tube or Electric equipment that harmonic wave Check that the grounding is completely insulated.)
Indicate or Display:
Indicate or Display:
Indoor Unit :
Operation LED
Flash
Flash
,
,
Timer LED
Flash
Flash
Swing LED
Flash
Flash
Outdoor Unit :
LED1
Flash,
LED6
1 8TIMES Blink (Indoor Unit address)
ERROR CODE :
E:04
E:04
2
2
2
06-09
Содержание AO54FJ
Страница 5: ...1 TEST RUN TM SERIES R410A ...
Страница 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Страница 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Страница 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Страница 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Страница 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Страница 128: ...7 INSTALLATION TM SERIES R410A ...
Страница 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Страница 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Страница 155: ...COMPACT DUCT TYPE MODELS AR7 AR9 AR12 AR14 AR18 AR22 9 3 WIRING DIAGRAM 9 3 1 INDOOR UNIT 09 06 ...
Страница 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Страница 157: ...MODELS AR36 AR45 09 08 ...
Страница 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Страница 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Страница 160: ...MODELS AU36 AU45 AU54 09 11 ...
Страница 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Страница 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Страница 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...
Страница 164: ...COOLING ONLY TYPE MODEL AO54FJ 09 15 ...