4. Tightness test
(1) After completing all piping connection, always carry out an air tight test to check and confirm that there is no gas leakage.
Charge the piping with nitrogen to within the sealing test pressure (4.15 MPa). After 24 hours, check that the pressure has
not fallen. Make sure to add the pressure to both gas pipe and liquid pipe. Perform the leak test on all flared and brazed parts.
Note: When the ambient temperature changes 5 deg. , the test pressure changes 0.07MPa.
(2) After tightness test, please insulate the connecting portion, apply the enough insulation to avoid any gap.
5. Vacuum process
(1)
Do not purge the air with refrigerant but use a vacuum pump to remove air from the indoor units and connection pipes!
(2) Remove the cap, and connect the gauge manifold and the vacuum pump to the charging valve by the service hoses.
(3) Vacuum the indoor unit and the connecting pipes until the pressure gauge indicates -76 cmHg.
(4) When -76 cmHg is reached, operate the vacuum pump for at least 1 hour.
(5)
If necessary, add the refrigerant for the appropriate amount after the vacuum process is completed
(Refer to next page "ADDITIONAL CHARGE").
6. Additional charge
(1) Be careful, don't charge with wrong
refrigerant!
(2) When moving and installing the air conditioner, do not mix gas other than the specified refrigerant inside the refrigerant
circuit.
(3) When charging the refrigerant, always use an electronic balance for refrigerant charging. (to measure the refrigerant by weight)
(4) A
lways charge from the liquid phase side whose composition is stable.
(5) Always add the refrigerant for the appropriate amount. (For the calculation method, please refer to 7-1"ADDITIONAL
CHARGE")
(6) Either larger or smaller refrigerant charge amount leads to the cause of trouble.
(7) For after service purpose, the added refrigerant charge amount and the calculation shall be indicated firmly on the service
label over the side panel.
(6) Disconnect the service hoses and fit the cap to the charging valve.
(7) Remove the blank caps, and fully open the spindles of the 3-way valves with a hexagon wrench.
(8) Tighten the blank caps of the 3-way valves to the specified torque.
Liquid pipe (3-way valve)
Gas pipe (3-way valve)
Blank cap
19.6 to 24.5 N·m
34.3 to 39.4 N·m
Charging cap
10 to 12 N·m
10 to 12 N·m
Gauge manifold
Vacuum
pump
Auxiliary pipe assembly
Charging
cap
Blank
cap
Hexagon
wrench
Operation
mode
Cooling
Heating
Check valve
pressure
High Pressure
Low Pressure
Check valve
Содержание AO54FJ
Страница 5: ...1 TEST RUN TM SERIES R410A ...
Страница 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Страница 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Страница 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Страница 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Страница 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Страница 128: ...7 INSTALLATION TM SERIES R410A ...
Страница 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Страница 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Страница 155: ...COMPACT DUCT TYPE MODELS AR7 AR9 AR12 AR14 AR18 AR22 9 3 WIRING DIAGRAM 9 3 1 INDOOR UNIT 09 06 ...
Страница 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Страница 157: ...MODELS AR36 AR45 09 08 ...
Страница 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Страница 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Страница 160: ...MODELS AU36 AU45 AU54 09 11 ...
Страница 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Страница 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Страница 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...
Страница 164: ...COOLING ONLY TYPE MODEL AO54FJ 09 15 ...