Trouble shooting 28
OUTDOOR UNIT
OUTDOOR UNIT
Error Method:
Error Method:
Trip terminal L abnormal
Detective Actuators:
Detective Actuators:
Abnormal condition of TR PWB ASSY is
monitored by Control PCB detector circuit.
Detective details:
Detective details:
When Trip terminal inside IPM Module becomes Lo At the compressor start - up,
it is judged as a start - up error. LED indicates error and outputs and the error
information to the network.
Forecast of Cause
Forecast of Cause: 1. Connection of electrical parts
2. TR PWB ASSY / control PCB defective
3. Check Compressor
Check Point 2 : Diagnosis of Control PCB / TR PWB ASSY
Check Point 2 : Diagnosis of Control PCB / TR PWB ASSY
1.Check the supply voltage from Control PCB to IPM
Check DC+15.0V between terminal 1 - 2 of main PWB CN16 (IPM Power supply)
If the voltage does not appear,replace Control PCB
2.Check the voltage at Trip Terminal (To Check TR PWB)
Remove the connector CN14 between TR PWB ASSY - Control PCB.
Check DC+5V between terminal 1 - 2 ,2 - 3 of CN14 (Connector side)
3.Check TR PWB ASSY (Check Transistor Module).
Remove the cable from each terminal and check the continuity.
If any abnormal condition is found, replace TR PWB ASSY.
Check Point 1 : Connection of electrical parts
Check Point 1 : Connection of electrical parts
Check if each electrical parts are connected correctly.
Check if Connector CN14 between TR PWB ASSY and control PCB.
Check if TR PWB ASSY has a corrosion or shorted mark.
Rework if connector is incorrectly wired, or loose.
Replace TR PWB ASSY if any abnormal condition is found on PCB.
P
U
V
W
N
TR PWB ASSY
1
9
(1)BROWN DC+5.0V
(2)RED GND
(3)ORANGE Lo(+DC5V)
Indicate or Display:
Indicate or Display:
Indoor Unit :
Operation LED
Flash
Flash
,
,
Timer LED
3 Times Blink
3 Times Blink
Swing LED
3 Times Blink
3 Times Blink
Outdoor Unit :
LED1
Flash
Flash
,
,
LED4
9
9
Time Blink
Time Blink
ERROR CODE: E:32
Outdoor unit grille side
Check Point 3 :
Check Point 3 :
Check Compressor
Check Compressor
Check the shortage between each U,V,W terminal and the main unit.
If it is shorted, the compressor is defective
Check the cut off between each U,V,W terminal.
If it is open, the compressor is defective.
06-31
(+),( - ) shows the terminal of the meter
14 15
N ( )
N ( )
W ( )
V ( )
14 15
U ( )
P ( )
V ( )
U ( )
W ( )
V ( )
U ( )
P ( )
W ( )
V ( )
U ( )
W ( )
Normal
resistance
value
COMP
TERMINAL
P / N
TERMINAL
Multimeter
Resistance value
U
1M Ohm or greater
U
W
V
P
W
V
N
The resistance value is changes in a type
of the tester (Digital or Analogue)
and internal resistance.
Confirm method for analog meter.
Simple confirm method for digital meter.
Содержание AO54FJ
Страница 5: ...1 TEST RUN TM SERIES R410A ...
Страница 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Страница 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Страница 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Страница 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Страница 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Страница 128: ...7 INSTALLATION TM SERIES R410A ...
Страница 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Страница 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Страница 155: ...COMPACT DUCT TYPE MODELS AR7 AR9 AR12 AR14 AR18 AR22 9 3 WIRING DIAGRAM 9 3 1 INDOOR UNIT 09 06 ...
Страница 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Страница 157: ...MODELS AR36 AR45 09 08 ...
Страница 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Страница 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Страница 160: ...MODELS AU36 AU45 AU54 09 11 ...
Страница 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Страница 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Страница 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...
Страница 164: ...COOLING ONLY TYPE MODEL AO54FJ 09 15 ...