Check Point 1: Check Circuit connection
Check Point 1: Check Circuit connection
SERVICE
SERVICE
PARTS INFORMATION 9
PARTS INFORMATION 9
S V
CN1
CN1
AC LINE
-
-
1
1
CN1-3
Check Point 2: Check Solenoid coil
Check Point 2: Check Solenoid coil
Remove connectors CN4,CN5, Check if the resistance of coil.
Normal resistance value of each coil :1.5k (approx)
If the resistance value is abnormal Due to cut- off etc. replace
the solenoid coil.
Check Point 3: Check voltage of Solenoid coil
Check Point 3: Check voltage of Solenoid coil
If the voltage is abnormal, replace Control PCB.
During normal operation, the voltage between 1- 2 of
CN4 / CN5 is OV. It becomes 220V+ - 20V when it is ON
due to the protection operation etc..
Check Point 4: Check operation of Solenoid Valve
Check Point 4: Check operation of Solenoid Valve
Pipe (In)
Pipe (Out)
Pipe (In)
Pipe (Out)
Pipe (In) TEMP. Hi,
Pipe (Out) TEMP.Normal
Pipe (In) TEMP. = Pipe (Out) TEMP.
AC
AC
SOLENOID COIL
SOLENOID COIL
Normal Operation
Protection Function ,
Pressure Balance condition (3ST)
If the location of valve is not proper, replace the valve.
Check the temperature difference between inlet and Out of the piping if it is function normal depending on the normal
operation control condition.
Check Point 4: Check when Bypass can not be released during norm
Check Point 4: Check when Bypass can not be released during norm
al operation.
al operation.
1.Remove the connector of the desired valve, and
check if the by pass is released.
If it is release, replace Control PCB.
(It is due to defective Relay or Shorted AC line.)
2.If it is not released by above item1., replace the valve.
Clogging due to oxidized film etc.
Deform due to over heating during the valve
installation.
P/No.
9900188016 (VALVE)
P/No.
9900189020 (Solenoid COIL 1)
P/No.
9900189013 (Solenoid COIL 2)
Hi TEMP.
Normal TEMP.
Hi TEMP.
Hi TEMP.
Open
CLOSE
Check Connectors CN4,CN5. Also check if cable is broken.
06-51
Содержание AO54FJ
Страница 5: ...1 TEST RUN TM SERIES R410A ...
Страница 14: ...2 FUNCTION OF PRINTED CIRCUIT BOARD TM SERIES R410A ...
Страница 39: ...3 INVERTER CONTROL TM SERIES R410A ...
Страница 45: ...4 OUTDOOR UNIT OPERATION CONTROL TM SERIES R410A ...
Страница 54: ...5 INDOOR UNIT OPERATION TM SERIES R410A ...
Страница 70: ...6 TROUBLE SHOOTING TM SERIES R410A ...
Страница 128: ...7 INSTALLATION TM SERIES R410A ...
Страница 140: ...8 REFRIGERANT CAUTION R410A TM SERIES R410A ...
Страница 149: ...9 APPENDING DATA1 UNIT TM SERIES R410A ...
Страница 155: ...COMPACT DUCT TYPE MODELS AR7 AR9 AR12 AR14 AR18 AR22 9 3 WIRING DIAGRAM 9 3 1 INDOOR UNIT 09 06 ...
Страница 156: ...LOW STATIC PRESSURE DUCT TYPE MODELS AR25 AR30 ARXB25 ARXB30 09 07 ...
Страница 157: ...MODELS AR36 AR45 09 08 ...
Страница 158: ...COMPACT CASSETTE TYPE MODELS AU7 AU9 AU12 AU14 AU18 09 09 ...
Страница 159: ...CASSETTE TYPE MODELS AU20 AU25 AU30 09 10 ...
Страница 160: ...MODELS AU36 AU45 AU54 09 11 ...
Страница 161: ...COMPACT WALL MOUNTED TYPE MODELS AS7 AS9 AS12 AS14 09 12 ...
Страница 162: ...WALL MOUNTED TYPE MODELS AS18 AS24 AS30 09 13 ...
Страница 163: ...HEAT PUMP TYPE MODEL AO54UJ 9 3 2 OUTDOOR UNIT 09 14 ...
Страница 164: ...COOLING ONLY TYPE MODEL AO54FJ 09 15 ...