AIMS Power
www.aimscorp.net
Battery type selector
Switch setting
Description
Boost / Vdc
Float / Vdc
0
Charger Off
1
Gel USA
14.0
13.7
2
AGM 1
14.1
13.4
3
AGM 2
14.6
13.7
4
Sealed lead acid /
LIFEPO4 lithium
14.4
13.6
5
Gel EURO
14.4
13.8
6
Open lead acid
14.8
13.3
7
Calcium
15.1
13.6
8
De-sulphation
15.5 (4 Hours then Off)
9
Not used
De-sulphation
The de-sulphation cycle (
switch position 8
) is a very dangerous setting if you do not know what you are
doing. Before attempting to use this cycle you must clearly understand what it does and when and
how you would use it.
What causes sulphation? This can occur with infrequent use of the batteries or if the batteries have been
discharged low enough that they will not accept a charge. This cycle is a very high voltage charge cycle
designed to try to break down the sulphated crust that is preventing the plates from taking a charge and
allowing the plates to clean up and accept a charge once again.
*Check the required charging specifications with the battery manufacturer. The chart above is just a guide.