AIMS Power
www.aimscorp.net
※Specifications in this manual are subject to change without prior notice
Sealed Lead Acid
14.4
13.6
Gel Euro
14.4
13.8
Open Lead Acid
14.8
13.3
Calcium
15.1
13.6
De-sulphation
15.5 for 4hrs
Remote Control
Yes. Optional
Bypass &
Protection
Input Voltage
Waveform
Sine wave (Grid or Generator)
Nominal Voltage
120Vac
Low Voltage Trip
85V±4%
Low Voltage re engage
90V±4%
High Voltage Trip
135V±4%
High Voltage re engage
130V±4%
Max Input AC Voltage
150VAC
Nominal Input
Frequency
60Hz (Auto detect)
Low Frequency Trip
Narrow:57±0.3Hz
Low Frequency re
engage
Narrow: 58±0.3Hz
High Frequency Trip
Narrow: 65±0.3Hz
High Frequency re
engage
Narrow: 64±0.3Hz
Output Short circuit
protection
Circuit breaker
Bypass breaker rating
(120Vac)
15A
30A
Mechanical
Specification
Mounting
Wall/Ground
M
ount
- Do not install upside down (top facing down)
Inverter
Dimensions(L*W*H)
14.25”x 8.7” x 7”
19.88” x 8.7” x 7.04”
Inverter Weight
38 lb
46 lb
Shipping
Dimensions(L*W*H)
20.47” x 12.6” x 12.2”
26.4” x 12.6” x 12.2”
Shipping Weight
42 lb
50 lb
Display
Status LEDs
Standard Warranty
1 Year
24