AIMS Power
www.aimscorp.net
2.5.9
Aud
ible
Alarm
Battery Voltage Low
Inverter green LED lit, and the buzzer beeps 0.5s every 5s.
Battery Voltage High
Inverter green LED lit, and the buzzer beeps 0.5s every 1s and Fault after
60s.
Invert Mode Overload
(1)110%<load<125%(±10%), No audible alarm in 14 minutes,
Beeps 0.5s every 1s in 15
th
minute and Fault after 15 minutes;
(2)125% <load<150%(±10%), Beeps 0.5s every 1s and Fault after 60s;
(3)Load>150%(±10%), Beeps 0.5s every 1s and Fault after 20s;
Over Temperature
Heat sink temp. ≥105ºC(221℉
), Over temp red LED Lighting, beeps 0.5s
every 1s;
14