28
Networking
Modbus TCP
The controller will accept a connection from a Modbus TCP master.
Controller Outputs
The Controller
’
s outputs are located at address 0 and contain one status word.
Controller Inputs
The Controller inputs are located at address 1024 and 1036. Address 1024 contains one control word and 1036 con-
tains the 20 character VIN.
Controller Outputs
Bits
15
14 13
12
11 10
9
8
7 6 5 4 3 2 1 0
Address 0
Handshake
Job Complete
Healthy Running
Process number
Bit
Name
Function
0
-
7
Process Number
Process number echo. Latched while it is in a job.
8
Running
Indicates the tool is running.
9
Healthy
Indicates the controller has no faults.
10
Not used
11
Not used
12
Job Complete
Indicates the job is complete. Will go off when Enable input goes off.
13
Not used
14
Not used
15
Handshake
Echo of the Handshake input
Controller Inputs
Bits
15
14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Address 1024
Handshake
Abort Enable
Process number
Bit
name
Function
0-7
Process Number
Process number input. The enable must be off to change the Process Number. On
a change to the Process Number the batch is also reset.
8
Enable
On the rising edge of Enable the tool will be enabled.
9
Abort
If Abort is on the tool will be disabled.
10
Not used
11
Not used
12
Not used
13
Not used
14
Not used
15
Handshake
Will be echoed to the Handshake output