Page 36 of 83
SK2018 PCG(H)-V/P-AECM-001
B.13.
Electrical Connection
It is recommended shielded line voltage and low voltage cables in electrically noisy areas.
Do not install fan coil unit in a location where electromagnetic waves may be directly emitted towards infra-red receiver
on the unit.
Install the unit and components as far away as is practical (at least 16.4 ft) from the electromagnetic wave source.
Use shielded sensor cable in where electromagnetic waves exist.
Install a noise filter if necessary.
Wiring Procedures:
1.
Open the terminal block cover by removing the 4 screws.
2.
Connect power cable to the terminal according to the wiring diagram.
3.
Connect room temperature sensor and coil temperature sensors to control box.
4.
Connect stepping motors.
5.
Connect receiver display.
6.
Connect wired wall-pad controller (optional).
7.
Slide the control box into the unit casing and attach with screws.
Figure 28
IMPORTANT NOTES
Please ensure the cable of the main powers supply is longer than 16.4ft from the control box
terminal block. This is to ensure the control box can be slid out easily during maintenance activities.
Always take safety precautions before wiring for mains supply. See section B.1, Safety Precautions.