Page 59 of 83
SK2018 PCG(H)-V/P-AECM-001
D.8.
Modulating Valve Control Under Energy Saving Mode
If the modulating valve is used, the water flow is adjusted from 0 to 100% according to the room temperature and set
temperature. The controller adjusts the modulating valve signal input from 0 to 10VDC by PID calculation every 10 seconds.
D.9.
Louver
For remote handset.
Whenever the indoor fan is running, the louver can swing or stop at the desired position.
Louver angle: 0~100 º, opens clockwise with widest angle at 100 º.
Swing angle: 35~100 º, opens clockwise to 68º. Below are the 4 fixed positions which can be set from wireless LCD handset.
Position
Angle against vertical
1
35 º
2
57 º
3
83 º
4
100 º
For wired wall pad
Louver angle: 0~100 º, opens clockwise, with widest angle at 100 º.
Swing angle: 35~100 º, opens clockwise to 68º. User may stop louver at any desired position between 35~100 º.
D.10.
Buzzer
If a command is received by the fan coil unit, the master unit will respond with 2 beeps for each setting, while the slave unit
will respond with 1 beep.
D.11.
Auto Restart
The system uses non-volatile memory to save the present operation parameters when system is turned off or in case of
system failure or cessation of power supply. Operation parameters are mode, set temperature, swing louver’s position, and
the fan speed. When power supply resumes or the system is switched on again, the same operations as previously set will
function.
D.12.
On/Off Switch On LED Display Panel
a)
This is a tact switch to select Cool→Heat→Off opera on mode.
b)
In COOL mode, the set temperature of the system is 75.2ºF with auto fan speed. There are no timer and sleep modes.
c)
In HEAT mode, the set temperature of the system is 75.2ºF with auto fan speed. There are no timer and sleep modes.
d)
Master unit that does not use a wall pad will globally broadcast.
NOTE
When button pressing is effective, the master unit buzzer will beep twice and the slave
unit will beep once.